Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01706
Parcel: 12514016A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM01706
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2003 EROSE1 WWM REVIEW Needs Review
09/09/2003 ELAINE ROSE ZONING REVIEW Needs Review
09/09/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Plan note references to the IRC throughout the plan set must be revised to reflect the applicable IBC references. The IRC code governs only 1 and 2 family dwellings.

2. Fire barrier walls and horizontal assemblies must have a fire resistive rating determined in accordance with IBC Table 302.3.3.

Sheet 3.1
1. Note 16 relating to garage door openings does not appear to apply to this project. Please delete.

Sheet 4.1
1. Provide the item number from IBC 719.1(2) for the vertical dwelling unit separation or the listing number for the wall assembly from an approved testing agency. Ref. IBC 708.1. The assembly specified must meet the IBC sound transmission classification criteria. Ref. IBC 1206.

2. Provide the item number from IBC 719.1(3) for the horizontal dwelling unit separation or the listing number for the horizontal assembly specified from an approved testing agency. Ref. IBC 710. The assembly specified must meet the IBC sound transmission classification criteria. Ref. IBC 1206.

3. Specify the listing number from an approved testing agency for the protection of the penetrations of fire rated assemblies. Ref. IBC 711.

4. The plan shows a 4" elevation differential from finish floor elevation to the porch slab at the entry condition. Please revise to provide an accessible entrance for the ground floor units. Ref. IBC 1105. Detail the threshold for compliance with IBC 1003.3.1.6.

Sheet 4.2
1. Provide a dimension for the stair width. Ref. IBC 1003.3.3.1.

2. The stair treads and riser dimension provided on the plan must comply with IBC 1003.3.3.1. The elevation of the first floor landing is called out as 99' 8". The elevation of the second floor landing is called out as 100' 0". Please resolve the 4" discrepancy. Treads and risers are required to be uniform. Ref. IBC 1003.3.3.1

3. Detail the handrail for compliance with IBC 1003.3.3.11.

4. Detail the guards for compliance with IBC 1003.2.12.1.

Sheet 5.1
1. Provide the ICBO report number for the proposed stucco system.

Sheet 6.1
1. Detail 23/D2 is mislabeled on the building sections. Please revise.

Sheet 7.1
1. Coordinate with structural to provide the design and specification of the steel header at the stair.

2. Note 5 refers to a detail not found on the plan. Please clarify.

Sheet 8.1
1. Provide the detail referenced in roof note 1.

STRUCTURAL COMMENTS
General
1. Provide the vertical gravity load design calculations.

Sheets 3.1, 4.1 and 4.2
1. The LTT20B holdowns shown in the holdown schedule as holdown 4 do not appear in the design calculations. Please clarify.

2. Specify the post sizes at footing types keynoted as 7, 8 and 9.

Sheets 3.1 and D1
1. Footings supporting 2 floors of light frame construction are required to have a depth of 18". Ref. IBC Table 1805.4.2.

Sheet S1
1. The code reference shown in note 2 at the nailing schedule is to the 1997 UBC. The code reference for the 2000 IBC is to Table 2304.9.1.

PLUMBING COMMENTS
Sheet P1
1. The references to the governing code in the notes should state the 1994 UPC with State amendments.

2. The fixture values for the water supply are to be taken from UPC Table 6-3. The fixture values for drainage piping are to be taken from UPC Table 7-3.

MECHANICAL COMMENTS
Sheet M1
1. The reference to the governing code in note 1 should state the 2000 IMC.

2. Please show the size route and point of termination for condensate disposal. Ref. IMC 307.2.

3. Please specify the provisions for outdoor ventilation air. Ref. IMC 403.

4. Please clarify if domestic range hoods are to be provided. If so, note size, material and point of termination. Ref. IMC 505. Through penetrations of horizontal assemblies must comply with IBC 711.

ELECTRICAL COMMENTS
Sheet E1
1. The references to the governing code in the notes should state the 1999 NEC.

2. Note that the receptacle on circuit A-14 at the kitchen countertop will be ground
fault circuit interrupter protected. Ref NEC 210-8 (a) (6).
ENERGY COMMENTS - The energy portion has been reviewed and approved.
09/09/2003 EROSE1 WATER REVIEW Needs Review
09/09/2003 EROSE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2003 ELAINE ROSE OUT TO CUSTOMER Completed