Permit Number: T03CM01679
Parcel: 113011100

Address:
3610 N VINE AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM01679
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2003 GERRY KOZIOL WWM REVIEW Denied DEQ called Pearl; we need receipt as built and number of fixture units on plubming plan. We have no septic records.
05/20/2003 GP BUILDING-RESIDENTIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Please specify nominal dimension and spacing of collar ties for new roof framing.

2. Specify the composition of the new roof.

PLUMBING COMMENTS
General
1. Please be advised that no septic records have been found. Please provide private sewage disposal permits and as built information. Ref. UPC 713, 714.

MECHANICAL COMMENTS
General
1. Show the bathroom exhaust fan, specify cfm rating and show size and path of termination. Ref. R303.

ELECTRICAL COMMENTS
General
1. The electrical dryer shown in the load calculations does not appear in the panel schedule. Please clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed