Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM01618
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The mop sink is not an approved location for the termination of the T&P relief of the water heater. Reference Section 608.5, UPC 1994 as amended by the State of Arizona. 2. A minimum head of 10 feet is required for testing of the waste and vent piping. Reference Section 712.2, UPC 1994. 3. The plumbing plans and isometrics show three floor sinks and three floor drains but only two floor sinks and two floor drains are scheduled. Please coordinate. 4. Appliances to be directly connected to the water supply system (e.g. P24, P25, P56, & P57) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. |
04/24/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/24/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations based on Table 403.3, IMC. 2. Provide adequate outside air to provide makeup air for the Type II hood. Reference Sections 304.1 and Table 403.3 (f), IMC 2000. 3. Relocate duct smoke detector to return duct. Reference Section 606.2.1, IMC 2000. 4. The backdraft damper shown in detail 2/A5 appears to violate the UL listing for the exhaust hood. Reference UL file MH18450 and Section 304.1, IMC 2000. 5. Provide listing information for the vibration isolator shown in detail 2/A5. Reference Section 506.3.3.4, IMC 2000. |
04/29/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
05/15/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/20/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/22/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
05/22/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |