Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM01618
Parcel: 14042075B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM01618
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The mop sink is not an approved location for the termination of the T&P relief of the water heater. Reference Section 608.5, UPC 1994 as amended by the State of Arizona.
2. A minimum head of 10 feet is required for testing of the waste and vent piping. Reference Section 712.2, UPC 1994.
3. The plumbing plans and isometrics show three floor sinks and three floor drains but only two floor sinks and two floor drains are scheduled. Please coordinate.
4. Appliances to be directly connected to the water supply system (e.g. P24, P25, P56, & P57) that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
04/24/2003 ROBERT SHERRY WATER REVIEW Approved
04/24/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations based on Table 403.3, IMC.
2. Provide adequate outside air to provide makeup air for the Type II hood. Reference Sections 304.1 and Table 403.3 (f), IMC 2000.
3. Relocate duct smoke detector to return duct. Reference Section 606.2.1, IMC 2000.
4. The backdraft damper shown in detail 2/A5 appears to violate the UL listing for the exhaust hood. Reference UL file MH18450 and Section 304.1, IMC 2000.
5. Provide listing information for the vibration isolator shown in detail 2/A5. Reference Section 506.3.3.4, IMC 2000.
04/29/2003 GERRY KOZIOL WWM REVIEW Approved
05/15/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
05/20/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/22/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
05/22/2003 ANGIE SHOFFSTALL REJECT SHELF Completed