Permit Number: T03CM01617
Parcel: 126210350

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01617
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2003 ELAINE ROSE ZONING REVIEW Needs Review
04/24/2003 EROSE1 NPPO REVIEW Needs Review
04/24/2003 EROSE1 FIRE REVIEW Needs Review
04/24/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS:

Sheet A00.00

1. The revised sheet identifies a Type V-B building. The structural engineer confirms that the building is constructed of all non-combustible materials. Please review and clarify. Reference IBC 106.1.1.

Sheet A00.40

1. Detail 9 horizontal dimensions are not in agreement with Detail 13. Please coordinate. Reference IBC 106.1.1.



Sheet A00.50 / A00.51

1. Please identify location on the plans for the proposed new retaining wall shown on the structural drawing and location of existing retaining walls. Reference IBC 106.1.1.

2. Please indicate the existing property line retaining walls that impact the installation of the new ATM foundations and other new work. Reference IBC 106.1.1.

3. Please provide sign to identify the clearance beneath the ATM canopy. Reference IBC 106.1.1.

Sheet A12.00

1. Detail 13, Equipment Platform, is for a wood roof. However, the existing roof is steel and concrete. Please coordinate. Reference IBC 106.1.1.

STRUCTURAL COMMENTS:

Sheet S1.0

1. Please provide a sealed letter for the proposed deferred design submittal including the design professional's as well as owner's seal and signature for acceptance by the Building Official. Reference IBC 106.3.4.

Sheet S1.2

1. The Architectural Site Plan does not indicate new retaining walls. However, there is an existing retaining wall in close proximity of the new ATM canopy foundation. Please review and clarify. Reference IBC 1604.4.

Sheet S3.0 / S-4

1. The mechanical drawings indicate roof mounted equipment weights that exceed these shown on the structural drawings. Motorized equipment weights shall be multiplied by a 1.2 factor to obtain the design equipment weight. In addition, the weight of the equipment support platform and or flashing skirt shall be added to the design weight. Design calculations and or drawings have not been submitted for the existing roof system ability to support the new imposed loads. Please review and clarify. Reference IBC 1607.8.2, IBC 1604.4 and IBC 3402.2.

2. The proposed metal deck through-bolts proposed to support the new roof top screen wall appear to occur at a spacing that is not possible to coordinate with the location of existing metal deck flutes. Accordingly, without some kind of make-up piece for installation tolerance, the proper installation of the through-bolts may be difficult to accomplish. Consequently, the screen may be subject to excessive deflection or wobble. Please review and clarify. Reference IBC 1604.4.

3. Detail 215 does not match the screen wall. Please review and clarify. Reference IBC 106.1.1.

Calculations

1. Please clarify the numerical value for all the terms required to determine the qs = basic wind pressure and the 1.29 factor. Reference IBC 106.1.1.

PLUMBING COMMENTS:

Sheet M3.2

1. Identify on the drawing, code compliance with the 2000 UBC and 1999 IECC and 1994 UPC as adopted by the City of Tucson. Reference IBC 106.1.1.

MECHANICAL COMMENTS:

Sheet M9.1

1. Identify on the drawing, code compliance with the 2000 IBC, 2000 IMC and 1998 IECC as adopted by the City of Tucson. Reference IBC 106.1.1.

ELECTRICAL COMMENTS:

Sheet E01.01

1. Please provide catalog cuts of proposed exterior light fixtures for compliance with the City of Tucson Outdoor Lighting Code. Reference IBC 106.1.1.

2. The exterior discharge of all exits shall have emergency illumination. The new exit from the training room and the northwest exit do not have emergency illumination of the exit discharge. Please review and clarify. Reference IBC 1003.2.11.2.

ACCESSIBILITY COMMENTS;

Sheet A08.00

1. Please review and clarify ADA required dimensions for clearance at the grab bars and the proposed paper dispenser shown in Elevation 3. Reference IBC 1108 and ANSI 117.1.

Sheet A02.01-A / A11.00

1. Please identify the ADA teller station on the plan and provide dimensioned cross section and elevation details of the station for compliance. Reference IBC 1108.12.3 and ANSI 117.1
04/24/2003 EROSE1 WWM REVIEW Needs Review
04/24/2003 EROSE1 ENGINEERING REVIEW Needs Review
04/24/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2003 ELAINE ROSE OUT TO CUSTOMER Completed