Permit Number: T03CM01565
Parcel: 115040620

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM01565
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2003 JIM EGAN FIRE REVIEW Approved
03/28/2003 ANY PLUMBING-COMMERCIAL REVIEW Stopped
03/28/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. It appears that the water heater should be on a 240 V receptacle.
2. Provide lighting fixture schedule/cut sheets.
3. Provide a circuit for the smoke detector on the Panel Schedule.
4. Rework load calculations such that 100% of the appliances will run at the same time, or justify otherwise. On a small laundry room such as this serving apartments, this is a likely situation.
5. Show the location of Panel A and other equipment as necessary.
6. Show the rating of the existing service.
7. Show load calculations for the service, including all the loads on that service.
8. Clarify whether Panels 1331 and 1329 are new or existing.
9. Address grounding per NEC 250-32, Two or More Buildings Supplied from a Common Service.
10. Address Grouping of Disconnects per NEC 230-72.
03/28/2003 ANY WWM REVIEW Stopped
03/28/2003 ANY MECHANICAL-COMMERCIAL REVIEW Stopped
03/28/2003 ANY WATER REVIEW Stopped
03/31/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
03/31/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.
05/03/2004 ELAINE ROSE ZONING REVIEW Stop

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2003 ANY APPROVAL SHELF Stopped
03/28/2003 ANY OUT TO CUSTOMER Stopped
03/28/2003 ANY REJECT SHELF Stopped