Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM01496
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide air relief system for evaporative coolers. Reference Sections 304 and 601, IMC 2000. 2. Show how access is provided to the rooftop equipment. Provide sufficient detail to show that the installation meets the applicable codes. Clarify location of access ladder. Reference Section 306.5, IMC 2000. |
| 09/25/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide overflow drains. The overflow drains are to have their inlet 2" above the low point of the roof drains and to be piped independent of the roof drains. If overflow scuppers are to be installed, provide dimensions. Reference Section D 1.1 (d), UPC 1994. |
| 09/30/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/30/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |