Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM01496
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/04/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1994. 2. Provide calculations demonstrating compliance to Section 403, IMC. With evaporative coolers being used, all that is needed is to show that the total amount of air supplied to the space is at least equal to the amount of outside air required by Table 403.3, IMC 2000. 3. Provide mechanical design for installation of evaporative coolers. Include mounting method, ductwork and diffusers, air relief system, and equipment operational data. Reference Sections 304 and 601, IMC 2000. 4. Show how access is provided to the rooftop equipment. Reference Section 306.5, IMC 2000. |
| 09/04/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate Roof Drain Rise Diagram with drain leaders shown on Footing Plan. 2. Provide overflow drains. The overflow drains are to have their inlet 2" above the low point of the roof drains and to be piped independent of the roof drains. Reference Section D 1.1 (d), UPC 1994. 3. Clarify the relationship of the existing roof to scuppers #5 and # 7; does the existing roof drain to these scuppers? 4. Provide plumbing design for water supply and drains for the new evaporative coolers. Indicate how the new plumbing relates to the existing plumbing system and include information sufficient to show that the water supply is sized in accordance with Section 610.1, UPC 1994. |
| 09/12/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/23/2003 | ASHOFFS1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/23/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |