Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM01496
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Unprotected skylights are not allowed in Type 1B construction. Reference section 710.4 IBC. Provide specifications and or Evaluation Report number for skylights complying with Type 1B construction. 2. Proposed wood framing for skylight shaft is not allowed in Type 1B construction. See detail Library A-4. Reference section 603 IBC. Revise plans 3. A Class B roof covering is required for proposed construction. Specify classification. Reference section 1505 IBC 4. Provide an exit plan including required panic hardware, exits, and distances. |
| 07/02/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide roof drainage calculations, including overflow drainage. Reference Appendix D, UPC 1994. |
| 07/02/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1994. 2. Clarify type of HVAC equipment to be used on the project. The HVAC Plan on sheet M1shows two 3-ton rooftop air conditioners but a note on that sheet also specifies matching the existing "swamp coolers." Reference Section 302.3, Uniform Administrative Code 1994. 3. Provide calculations demonstrating compliance to Section 403, IMC. |
| 07/03/2003 | Loren Makus | ENGINEERING | REVIEW | Approved | |
| 07/08/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | TO: Larry B. Justice 252 Park West Drive Pittsburg, PA 15275 (800) 866-6287 FROM: Peter McLaughlin Senior Planner Development Services FOR: Patricia Gehlen Principal Planner Development Services Dept. PROJECT: T03CM001496 Mausoleum Corridor Addition 5801 E. Grant Road Site Plan Review (1st review) TRANSMITTAL: July 8, 2003 COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. The site plan does not show all of the interior lot lines. It appears that the proposed addition may cross or come close to crossing existing lot lines. Buildings may not cross lot lines. A lot combination may be required. Please provide documentation (see attached assessors lot combo form and copy of covenant required). DS 2-02 2. Please provide a copy of the last approved site plan. A site plan with all its specifications is required per DS 2-02. If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608. |
| 07/09/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Provide panel and circuit numbers for all new electrical loads. 2. Provide panel schedule, feeder load calculation, and line diagram and service entrance calculations, as necessary. 3. Specify HVAC equipment so that it may be evaluated for electrical compliance, on such items such as conductor size, overload protection and sizing, ground fault and short-circuit protection and sizing. 4. Rooftop GFCI shall be circuited per NEC 210-63, not on load side of disconnect. 5. Show location of panel and electrical service. 6. Indicate whether the above on Comment 5 are new or existing. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 07/10/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |