Permit Number: T03CM01482
Parcel: 106030450

Address:
102 E MOHAVE RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM01482
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 0.1
1. Where the fire separation distance between the A-3 and R-2 occupancies is less than allowed by IBC Table 602, exterior wall construction and protection must be per IBC Sec. 704.

Sheet 1.5
1. Please indicate the location of the attic access. Ref. IBC 1208.2.

2. Specify the smooth, hard, nonabsorbent surface extending a minimum of 6 inches onto the walls of the toilet room. Ref. IBC 1209.2.

3. Keynote 3, specifying 2 hour wall construction, must reference an item number from IBC Table 719.1 (2) or an approved testing agency listing number. Please specify where this condition is to occur and coordinate with architectural comment 1, Sheet 0.1.
Sheet 1.6
1. Please detail the post to foundation connection and the post to beam connection shown in Section 2.

2. Address the fireblocking requirement for concealed spaces. Ref. IBC 716.

Sheet 6.3
1. Show by size, type and location compliance with required net free ventilating area. Ref. IBC 1202.2


STRUCTURAL COMMENTS
General
1. Fire resistive construction elements to be provided may alter the design load criteria. Please review the rated assemblies for conformance and compatibility with the structural design.


PLUMBING COMMENTS
Sheet 15..6
1. Please revise the fixture unit value assigned for clothes washer water. Ref. UPC Table 6-3.


MECHANICAL COMMENTS
Sheet 15.5
1. Indicate the point of termination for condensate disposal piping. Ref. IMC 307.2.1.


ELECTRICAL COMMENTS
Sheet 16.2
1. Circuits 9 and 6 on Panel H were not found on the plan. Please clarify.

2. Keynote 13 appears to reference a disconnect for the air handler but does not appear in the keynotes. Please clarify.

Sheet 16.3
1. Please provide fixture cut sheets with photometrics to determine compliance with the outdoor lighting code requirements.


ENERGY COMMENTS
General
1. Provide the interior lighting power analysis. Ref. IECC Table 705.4.
04/29/2003 EROSE1 WATER REVIEW Needs Review
04/29/2003 EROSE1 FIRE REVIEW Needs Review
04/29/2003 EROSE1 ENGINEERING REVIEW Needs Review
04/29/2003 EROSE1 WWM REVIEW Needs Review
04/29/2003 ELAINE ROSE ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed