Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03CM01482
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet 0.1 1. Where the fire separation distance between the A-3 and R-2 occupancies is less than allowed by IBC Table 602, exterior wall construction and protection must be per IBC Sec. 704. Sheet 1.5 1. Please indicate the location of the attic access. Ref. IBC 1208.2. 2. Specify the smooth, hard, nonabsorbent surface extending a minimum of 6 inches onto the walls of the toilet room. Ref. IBC 1209.2. 3. Keynote 3, specifying 2 hour wall construction, must reference an item number from IBC Table 719.1 (2) or an approved testing agency listing number. Please specify where this condition is to occur and coordinate with architectural comment 1, Sheet 0.1. Sheet 1.6 1. Please detail the post to foundation connection and the post to beam connection shown in Section 2. 2. Address the fireblocking requirement for concealed spaces. Ref. IBC 716. Sheet 6.3 1. Show by size, type and location compliance with required net free ventilating area. Ref. IBC 1202.2 STRUCTURAL COMMENTS General 1. Fire resistive construction elements to be provided may alter the design load criteria. Please review the rated assemblies for conformance and compatibility with the structural design. PLUMBING COMMENTS Sheet 15..6 1. Please revise the fixture unit value assigned for clothes washer water. Ref. UPC Table 6-3. MECHANICAL COMMENTS Sheet 15.5 1. Indicate the point of termination for condensate disposal piping. Ref. IMC 307.2.1. ELECTRICAL COMMENTS Sheet 16.2 1. Circuits 9 and 6 on Panel H were not found on the plan. Please clarify. 2. Keynote 13 appears to reference a disconnect for the air handler but does not appear in the keynotes. Please clarify. Sheet 16.3 1. Please provide fixture cut sheets with photometrics to determine compliance with the outdoor lighting code requirements. ENERGY COMMENTS General 1. Provide the interior lighting power analysis. Ref. IECC Table 705.4. |
04/29/2003 | EROSE1 | WATER | REVIEW | Needs Review | |
04/29/2003 | EROSE1 | FIRE | REVIEW | Needs Review | |
04/29/2003 | EROSE1 | ENGINEERING | REVIEW | Needs Review | |
04/29/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
04/29/2003 | ELAINE ROSE | ZONING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/29/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |