Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM01471
Parcel: 128010040

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01471
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied
04/09/2003 EROSE1 NPPO REVIEW Needs Review
04/09/2003 EROSE1 FIRE REVIEW Needs Review
04/09/2003 EROSE1 WWM REVIEW Needs Review
04/09/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/09/2003 ELAINE ROSE OUT TO CUSTOMER Completed