Permit Number: T03CM01429
Parcel: 10714139F

Address:
81 W JACINTO ST

Review Status: Completed

Review Details: SITE

Permit Number - T03CM01429
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2003 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: April 10, 2003
ACTIVITY NUMBER: T03CM01429
PROJECT NAME: Office Building for Gary Repovsch
PROJECT ADDRESS: 81 West Jacinto Street
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. The lot dimensions on the plan are incorrect. The length of the property scales to 137' and currently on the plan the length of the parcel is labeled at 147'. Revise plan as necessary to depict actual length of the property. DS 2-02.2.1.A.5.

2. Add a note on the plan, "All roof down spouts on all structures must be routed under any adjacent sidewalk." Sidewalks must be flood free for up to the 10-yr. event. DS 2-08.4.1.E

3. New development will provide on-site refuse storage, collection, and pickup areas with service access from within the tract or from an alley adjacent to the tract. For a new development to have curbside pick up, written permission is required from John Clark of the Solid Waste Department. DS 6-01.4.1.A.
04/10/2003 PATRICIA GILBERT SANITATION REVIEW Denied New development will provide on-site refuse storage, collection, and pickup areas with service access from within the tract or from an alley adjacent to the tract. For a new development to have curbside pick up, written permission is required from John Clark of the Solid Waste Department. DS 6-01.4.1.A.
04/11/2003 JIM EGAN FIRE REVIEW Approved
04/25/2003 DAN CASTRO HANDICAP-SITE REVIEW Approved
04/25/2003 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next,
submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Lot dimensions shown on the plan are 60.05' by 147', which totals 8,827.35 square feet. The gross site area noted under the site data block is 8,167 square feet. Revise to show correct gross site area. (D.S. 2-02.2.1.A.5)

2. Minimum building setback required from the street lot line is 24 feet. Revise note on plan as required.
(D.S. 2-02.2.1.A.7)

3. Provide a copy of the recorded ingress/egress easement and a copy of the last approved site plan for the lot east of the subject property. (D.S. 2-02.2.1.A.8)

4. If applicable, provide type, size, and height of existing and proposed free standing signage (including billboard) and outdoor lighting. (D.S. 2-02.2.1.A.13, & .25)

5. Note the zoning classification for the property to the east (O-3). (D.S. 2-02.2.1.A.28)

6. Revise the floor area ratio calculation to be based on the correct gross site area (bldg. area/gross site area).

7. All requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A)

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
04/28/2003 JOE LINVILLE NPPO REVIEW Denied The NPPO Exception Application has been reviewed.
If any protected plants existing on the site will be removed, they should be replaced or transplanted. This would constitute non-substantial impact. Show any protected plants to be retained or replacement plants on the landscape plan.
04/28/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) A five-foot high screen is required between the parking areas on the site and and adjacent O-3 zoned properties.
LUC Table 3.7.2-I

2) The refuse storage area must be screened from adjacent O-3 properties. LUC Table 3.7.2-I

3) Revise landscaping note 4 to include adjacent street right- of-way areas. LUC 3.7.2.4.A

4) Landscape areas should be designed to also serve as water harvesting areas. Per LUC 3.7.4.3.B "indicate use of
all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area."

5) The landscape plan may require revision in order to comply with Native Plant Preservation requirements. LUC 3.8

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2003 TAMI ACHONG OUT TO CUSTOMER Completed