Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01428
Parcel: 122081040

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM01428
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2003 Blanca Espino ENGINEERING REVIEW Denied 1. Sidewalk scuppers are required. At any point where a 10-year flood discharge starts to cross a sidewalk or a pedestrian access, the sidewalk/access shall be designed and constructed to convey the 10-year flood flows under the sidewalk/access.

2. As per the refuse enclosure location, a signed letter from John Clark or Environmental Services, indicating approval of location.
11/18/2003 Joseph Linville LANDSCAPE REVIEW Denied 1) Provide dimensions on the landscape plan for the street landscape borders. DS 2-07.2.2.A.2 The border width should not include the curb.

2) Per DS 2-06.3.8.I "Trees are to be planted an appropriate distance from refuse dumpster locations so that the tree canopy, at maturity, does not obstruct collection." and per DS 6-01.2.2.B.3 "A twenty-five (25) foot minimum height clearance, free of any overhead obstructions (wires, branches, etc.), shall be provided above the collection site".
Revise the plans to locate any proposed tree a minimum of 15-20 feet from the refuse pickup location.

3) A minimum of one additional canopy tree is required within the street landscape border. LUC 3.7.2.4

4) 6' high masonry walls are required to screen the refuse storage areas from adjacent properties and a 6' high screen is required to screen the opening from the street. Revise the landscape plan to call out all required screening heights, including any required to screen the parking areas.

5) The following standards from DS 6-01.0 may apply to the project:
Containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises.
&
Each service area is required to have a clear approach of fourteen (14) feet by forty (40) feet for the collection vehicle. The maximum back-up distance for the collection vehicle shall be forty (40) feet.

6) In order to comply with NPPO requirements a minimum of 6 replacement Prosopis velutina will be required. Include these on the landscape plan.
11/18/2003 JOE LINVILLE NPPO REVIEW Denied With 2 viable prosopis velutina on site the minimum preservation requirement is one. In lieu of that 2:1 mitigation would be acceptable to meet the minimum preservation requirement. In addition 2:1 mitigation is required for the 2 viable plants removed from site. The total mitigation required is five. these plants are to be shown on the landscape plan. DS 2-15.3.4.B
12/11/2003 ASHOFFS1 ZONING REVIEW Denied TO: Seaver /Franks Architects
2552 N. Alvernon Way
Tucson, AZ 85712
FROM: Peter McLaughlin
Senior Planner
Development Services Dept

FOR: Patricia Gehlen
Principal Planner
Development Services Dept

PROJECT: T03CM01428
New Multi-family Residence
2147 N. Isabel Drive

TRANSMITTAL: December 11, 2003

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. The maximum density allowed under R-2 zoning for development designator "K" is 15 units per acre. Please provide a density calculation showing the number of units per acre proposed. With 5 units proposed on a 15,000 square foot (0.34 acre) site the density would be calculated as follows: 5 units / 0.34 acres = 14.71 units per acre.
LUC 3.2.10
LUC 3.2.3.1.C

2. Add the square footage of vehicle use area to the plan and provide a lot coverage calculation showing the total lot coverage and the percentage of the lot covered by enclosed buildings and vehicle use area.
DS 2-02.2.2.A.3

3. Provide the building height above design grade elevation on the site plan
DS 2-02.2.1.A.6

4. Add the east-west (long) dimension of the buildings. DS 2-02.2.1.A.6

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/12/2003 ANGIE SHOFFSTALL REJECT SHELF Completed