Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01428
Parcel: 122081040

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM01428
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2003 JIM EGAN FIRE REVIEW Approved
05/07/2003 GERRY KOZIOL WWM REVIEW Approved
05/08/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide model energy code calculations that demonstrate conformance to the requirements of the International Energy Conservation Code (1998).
2. Provide listing information for exhaust fan EF-2. Reference Section 301.4, IMC 2000.
05/08/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The governing plumbing code is the 1994 Uniform Plumbing Code with State of Arizona Amendments.
2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC.
3. Include the elevation difference between the water meter and the highest fixture or outlet in your water pressure calculations.
05/08/2003 ROBERT SHERRY WATER REVIEW Passed
05/13/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
05/27/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide method and details for fire partition penetrations. Reference section 714 IBC
2. Structural calculations are to utilize the 2000 IBC for design. See computer printouts. Provide revised calculations
06/02/2003 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required prior to building plan approval.
06/02/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Coordinate riser diagram with number of units on title page. Sheet A1 depicts 5 units. Electrical Riser Diagram has provisions for 3 new units.
2. Service is rated 400A, which does not appear to be sufficient for (5) units @ 82 A each.
3. Please blow up the Riser diagram if possible. Out standards are Font Size #10, which is just over 1/8" high characters.
4. Understood that it can take awhile to get TEP available fault current for single phase services, but please indicate AFC or start the process with TEP and have the Contractor follow up with this information. Of special concern is the 100A panels, for example the panel in Unit C which is only a few feet from the Service Entrance Equipment.
5. Bedroom receptacles shall be AFCI protected per NEC 210-12 (b).
6. It appears that another outlet is needed on the east wall to meet the spacing requirements of 210-52.
7. Per 210-52 (b) (3), kitchen countertop receptacles shall be supplied by not less than two small appliance branch circuits.
8. Please add the following to #11 in the Electrical Specifications: "All exterior lighting fixtures shall comply with the current Lighting Ordinance."

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2003 DELMA ROBEY OUT TO CUSTOMER Completed