Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03CM01421
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet 0.1 1. The code analysis data indicates an allowable area of 13,000 s.f. for the R-2 / V-B apartments. IBC Table 503 provides for an allowable area of 7,00 s.f. for R-2 occupancies of V-B construction. Please address. 2. Where the fire separation distance between the A-3 and R-2 occupancies is less than allowed by IBC Table 602, exterior wall construction and protection must be provided in accordance with IBC Section 704. Sheet 1.1 1. Walls separating dwelling units in the same building require fire partitions as specified in IBC Section 708. Refer also to IBC 310.3. 2. Keynote 7, shown at the counter top in floor plan B, appears to be mislabeled. Please clarify if the intended reference is to keynote 4 Sheet 1.2 1. Provide a width dimension for the stairways. Ref. IBC 1003.3.3.1. 2. Provide dimensions for stair treads and risers. Ref. IBC 1003.3.3.3. 3. Provide dimensions for the stairway landings. Ref. IBC 1003.3.3.4. 4. Indicate the item number from IBC Table 719.1(2) or the approved testing agency listing number for the dwelling unit fire partitions. Ref. IBC 708. Address continuity, openings, penetrations and joints. Sheet 1.3 1. Indicate the item number from IBC Table 719.1(2) or the approved testing agency listing number for the dwelling unit fire partitions. Ref. IBC 708. Address continuity, openings, penetrations and joints. Sheet 1.4 1. Provide complete construction details for the stairways and guards. Refs. IBC 1003.2.12 and 1003.3.3.1 through 1003.3.3.11. 2. Indicate the item number from IBC Table 719.1(3) or the approved testing agency listing number for the fire resistant horizontal assembly. Address continuity, penetrations and joints. 3. Address the fire blocking and draft stopping requirements for concealed spaces. Ref. IBC 716. 4. Please address the requirement for parapets on exterior building walls. Ref. IBC 704.11. 5. Sound transmission class of not less than 50 must be provided for vertical and horizontal assemblies separating dwelling units. Ref. IBC 1206. 6. Please specify the fire classification for the roof assembly. Ref. IBC 1505. Sheet 1.7 1. Provide the penetration details for the fire resistant horizontal assemblies. Sheet 6.2 1. Show by type, size and location compliance with required net free ventilating area. Ref. IBC 1202.2. STRUCTURAL COMMENTS General 1. Fire resistive construction elements to be provided may alter the design load criteria. Please review the rated assemblies for conformance and compatibility with the structural design. PLUMBING COMMENTS Sheet 15.6 1. Specify cross connection control for the four hose bibbs shown on the plumbing plan. Ref. UPC 603.3.7. MECHANICAL COMMENTS Sheet 15.5 1. Indicate that mechanical equipment will be permanently marked to identify the area served. Ref. IMC 304.10. 2. Indicate point of termination for condensate disposal piping. Ref. IMC 307.2.1. ELECTRICAL COMMENTS Sheet 16.2 1. Keynote 10 appears to apply to the apartment condenser unit but was not shown on the plan. Please clarify. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
| 04/29/2003 | ELAINE ROSE | ZONING | REVIEW | Needs Review | |
| 04/29/2003 | EROSE1 | ENGINEERING | REVIEW | Needs Review | |
| 04/29/2003 | EROSE1 | FIRE | REVIEW | Needs Review | |
| 04/29/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 04/29/2003 | EROSE1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |