Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM01380
Parcel: 113070470

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM01380
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2003 ELAINE ROSE ZONING REVIEW Needs Review
04/10/2003 EROSE1 WWM REVIEW Needs Review
04/10/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Plans appear to be for shell construction only. Clarify that separate permits are required for tenant improvements.

2. Pl ans indicate occupancy group B. Notes specify retail which suggests occupancy group M. Please clarify.

Sheet A0.1
3. Ramps must have a minimum clear length of 60", ANSI A117.1, 405.7.3. Note that cross slopes may not exceed 1:48 ANSI A117.1, 405.3.

Sheet A1.1 through A1.2
1. Clarify if existing fixtures are to be removed.
Sheet A5.2
1. Clarify limits of handrail dimensions to address protruding object criteria defined in ANSI A117.1, 307.
Sheet A6.1
1. Clarify entrance lock hardware specifications. Ref. IBC 1003.3.1.8.

2. Please provide schedule for new storefronts. Detail C2/A6.1 references structural drawings. No detail for storefront appears in the structural sheets.

3. Clarify by detail how storefront wrap at column condition is to be constructed.

STRUCTURAL COMMENTS
General
1. Please provide the engineered truss design referenced in the building section as keynote 06176.

PLUMBING COMMENTS
Sheet A1.1 through A1.5
1. Please coordinate with architectural comment 1. Abandoned sewage disposal facilities must be plugged and capped. Ref. UPC 722.

MECHANICAL COMMENTS
Sheet M0.1
1. Provide SEER specification for the proposed heat pumps.

ELECTRICAL COMMENTS
Sheet E3.3
1. Circuit L-8 for the sign appears to be mislabeled on the plan. Revise.

ENERGY COMMENTS- The energy portion has been reviewed and approved.
04/10/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed