01/14/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Site, Grading and Drainage Report Review
REVIEWER: Doug Williams
DATE: 14 January 2004
ACTIVITY NUMBERS: T03CM01365/T03BU02538
T14S, R14E, Section 30

SUMMARY: Engineering Section has reviewed the Site and Grading Plan and Drainage Report resubmittals received on 19 December 2003. Approvals are not recommended at this time - resubmittal is required. Please address the following comments listed below, and provide a response letter specifically addressing each comment.

1. Please address the following previous comment: "Geotechnical and drainage report considerations and recommendations should address minimum structure setbacks from the retention/detention basin and associated discharges, to ensure no adverse impact will occur to adjacent structures and/or properties as a result of this development".
2. Clearly depict, label and provide the finished floor elevation of the existing adjacent structure on the site plan and grading/drainage plan, in accordance with the City of Tucson's Standards Manual for Drainage Design and Floodplain Management (SMDDFM) - Development Standard 10-02.0 - Section 14.2.4, and section 9.7 of the 2000 International Building Code (IBC), local amendment. For additional information, please go to: http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf

If you have any questions, I can be reached at 791-5550, ext. 1189 or Dwillia1@ci.tucson.az.us.

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department