| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2003 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning will approve building card upon aprroval by the commercial reviewers and upon final approval of the site plan. |
| 06/12/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1.Revise occupant load calculations for sales area to 1: 30. Reference Table 1003.2.2.2 IBC 2. Revise occupancy classifications to reflect use and revise code analysis sheet. Reference section 302 IBC 3. Provide water closets per Table 2902.1 IBC 4. Sales area requires two exits per section 1004 IBC. Revise plans 5. Landing to be a minimum width of the door. Reference section 1003.3.1.5 IBC. Revise plans. See sheet A-5 6. Twenty percent of construction cost is to go to providing accessibility. Reference section 3408.6 IBC Note: Existing bathroom does not comply with ANSI A117.1. Provide calculations and revise plans 7. Provide a complete lateral analysis of trailers in their proposed configuration. 8. Provide structural calculations and details for proposed openings in trailers. 9. Calculations indicate criteria for a foundation but there is none shown on the plans. 10. Clarify sleepers, etc.. within calculations 11. Provide calculations and detail for proposed opening in masonry wall. |
| 06/13/2003 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | Building plans may not be approved prior to Site Plan approval. |
| 06/13/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. AHU listed as single phase on Keynote 4 Sheet E1.0. and 3-phase on panel schedule. Clarify. If these are single phase units on a single circuit, have the tap conductors terminate in fuses at the respective disconnects per NEC 240-21(b) (2) (b). 2. Provide overload protection for AHUs, unless they are thermally protected. Suggest fusing the disconnect switches at 6A. 3. On Sheet E1.0, freezer controls are listed on Circuit P2-28,30,32. On panel schedule Circuits 28 & 30 are listed as spares, and Circuit 32 is part of a 3-phase feed to the AHUs. Please correct. 4. All three CU are listed in Keynotes 1,2, & 3 as having considerably more amperage than is typical per NEC Table 430-150. Please verify, and check circuitry and protection as necessary. 5. Identify circuit for maintenance receptacles for all rooftop units. 6. General notes 6 and 8 indicate all disconnects shall be fused. All equipment on key notes have non-fused disconnects. Please clarify. 7. Per NEC 250-32, where two or more buildings or structures are supplied from a common AC service, the required grounding electrodes shall be connected according to the provisions of this Article. Please comply. 8. Per NEC 250-50 (b), the metal frame of the Storage trailer(s) shall be bonded to the grounding electrode system. Make explicit that the code-required Exit Signage, both signs and emergency illumination, are included in the lighting circuit. If not, provide such circuit. See Sheet A-5. |
| 06/16/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listings and sizes of refrigeration equipment. 2. Show size, routing, and termination of condensate drains. 3. Provide Model Energy Code analysis. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 06/18/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |