Permit Number: T03CM01363
Parcel: 12111098A

Address:
5002 E ADAMS ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01363
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM01363 - 2ND REVIEW

7/16/03 5002 E. ADAMS ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER OR SEPTIC LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER AND SEPTIC SYSTEM
IF IT EXISTS.

FOUNDATION PLANS:

1. DIMENSION THE WALL THICKNESS, FOOTING WIDTH THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR
THE INTERIOR FOOTING. DETAIL THE REINFORCING , THE BOTTOM PLATE, AND IT'S CONNECTION TO THE FOUNDATION.

2. DIMENSION THE LANDING IN THE DIRECTION OF TRAVEL.

FLOOR PLAN:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS AND DOORS IN THE EXISTING SOUTH EAST BEDROOM.

3. HOW WILL EGRESS BE PROVIDED FOR THE SOUTH EAST BEDROOM IN COMPLIANCE WITH R310 ? ALSO, THE MASTER BEDROOM.

STRUCTURAL PLANS:

1. ROOF FRAMING NOTES ; 2-2X6 #2 D.F. HEADER IS INADEQUATE FOR THE 7' SPAN AT THE SOUTH WALL OF THE WORK SHOP.

2. ROOF FRAMING ; 2 X 6 @ 24" O.C. ARE INADEQUATE TO SPAN 19'- 4" OVER THE WORK SHOP.

3. ROOF FRAMING ; 2 X 10 @ 24" O.C. ARE INADEQUATE TO SPAN 18'-9" OVER THE NEW DAY ROOM.

4. ROOF FRAMING ; 4 X 4 #2 D.F. IS INADEQUATE TO SPAN 12'-2" AT THE SOUTH COVERED PORCH.



SECTIONS - DETAILS - MISC. NOTES:

1. G/5 ; A "PA-23" ISN'T APPROPRIATE FOR THIS USE. IS IT NECESSARY HERE?

2. C/5 ; PROVIDE AN H-2.5 , OR EQUAL , FOR THE PLATE/RAFTER CONNECTION.

MECHANICAL PLANS:

1. ALL HABITABLE ROOMS REQUIRE A SOURCE OF HEAT.

ELECTRICAL PLANS:

1. FIRST ELECTRICAL PLAN :
A. PROVIDE RECEPTACALES FOR THE EAST WALL OF THE DAY ROOM.
B. THE 220 V. RECEPTACLE ON THE SOUTH PORCH REQUIRES A CIRCUIT
C. A 110 V. RECEPTACLE IS REQUIRED TO SERVE THE SOUTH YARD.

2. SECOND ELECTRICAL PLAN :
A. PROVIDE RECEPTACLES FOR THE SOUTH WALL OF THE NEW ARIZONA ROOM.
B. ARE THE 220 V. RECEPTACLES ACCOUNTED FOR IN THE ELECTRICAL
CALCULATIONS ? TEN OF THEM ?
C. IS THE OPEN PATIO GOING TO BE CLOSED IN ?
D. PROVIDE A SWITCHED SOURCE OF LIGHT INSIDE AND OUTSIDE THE DOOR BETWEEN
THE SHOP AND THE PATIO.
E. PROVIDE A SWITCHED SOURCE OF LIGHT ON BOTH SIDES OF THE SOUTH DOOR OF
THE ARIZONA ROOM.



PLEASE USE ONLY ONE ELECTRICAL PLAN



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/18/2003 ANGIE SHOFFSTALL REJECT SHELF Completed