Permit Number: T03CM01358
Parcel: 121062480

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM01358
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2003 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM01358
5/06/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING:
MISSING ALONG NORTH WALL------IS EXISTING CLOSET ROOM BEING SHORTENED?

2. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS
SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312.

FLOOR PLANS:

1. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. DETAIL GABLE END BRACING CONNECTIONS.
MISSING FOR GARAGE

2. STEEL BEAM OVER 16' GARAGE OPENING IS NOT ADEQUATE---CHANGE OR SUBMIT CALCS.

3. GLULAM BEAM IS INADEQUATE FOR SPAN INDICATED -------CHANGE OR SUBMIT CALCS.

4. POINT LOAD FROM GLULAM APPEARS TO BE OVER DOORWAY, LINTEL INDICATED APPEARS TO BE INADEQUATE FOR LOAD IMPOSED

5. PROVIDE A BUILDING CROSS-SECTION.------MISSING FOR ADDITION

6. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- RAFTERS TO BEAM----AS INDICATED BEAM ABOVE ROOF LINE?
- HANGER TYPES

7. NOTE AND DETAIL TIE STRAPS FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED
ATTACHMENT TO FRAMING MEMBERS.

ELEVATIONS:

1. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.

ELECTRICAL PLANS:

1. INDICATE SIZE OF FEEDERS TO SUBPANEL AS WELL AS CONDUIT SIZE

2. NOTE THE LOCATION, TYPE AND AMPERAGE OF THE SUBPANEL. NOTE THE GROUNDING AND BONDING METHOD.

3. INDICATE SIZE AND LOCATION OF MAIN ELECTRICAL SERVICE

4. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2003 DELMA ROBEY OUT TO CUSTOMER Completed
05/07/2003 ANGIE SHOFFSTALL REJECT SHELF Completed