Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM01267
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2003 | ELAINE ROSE | ZONING | REVIEW | Needs Review | |
| 03/27/2003 | EROSE1 | WATER | REVIEW | Needs Review | |
| 03/27/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 03/27/2003 | EROSE1 | FLOODPLAIN | REVIEW | Needs Review | |
| 03/27/2003 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet SD2 1. Exterior grade shall slope away from the building perimeter at not less than a 2% drainage gradient. Please review and clarify control elevations for drainage swales and detail of handling storm drainage off of the roof so as not to drain over sidewalks. Reference IBC Sections 1803.3 and 3201.4. 2. Pima County Zoning Code is not effective in City of Tucson. Please review and revise. Reference IBC Section 106.1.1. 3. Grade contour is shown at 2400 feet elevation. However, the Pima County map indicates 2520 feet elevation in the vicinity. Please review and coordinate. Reference IBC Section 106.2. Sheet A-1 1. Provide detail of the perimeter exterior door thresholds. Reference IBC Section 1003.3.1.6. Sheet A-2 1. The occupancy separation for an automotive parking garage other than R-3 occupancy shall be not less than a 2-hour fire-resistive occupancy separation. Please review and coordinate. Reference IBC Section 302.1.1. 2. It appears that a two-hour fire-resistive rated building wall is identified abutting the property line. A one-hour rating is all that is required for a B-occupancy, Type-B building. Please review and clarify intent. Reference IBC Table 602. 3. Please clarify interior finish requirements per IBC Section 803. 4. Please identify toilet room floor finish, cove and the wall finish in the vicinity of water closets and urinals. Reference IBC Section 1209. 5. Please note that vacuum line shown here on the foundation plan shall be shown on the mechanical plan. Reference IBC Section 106.1.1. Sheet A-3 1. Identify the maximum occupant load under code information section on the drawing. Reference IBC Section 1003.2.2. Sheet A3.a 1. Coordinate the location of mechanical rooftop units with the mechanical plans. Reference IBC Section 106.1.1. 2. Please provide dimensions for the rooftop screen wall and provide cross-section showing lateral support details. Reference IBC Section 106.1.1. 3. Please note that water from a roof shall not drain over a sidewalk used by the public. Please review and clarify storm water drainage off the roof. Reference IBC Section 3201.4 4. Secondary roof drains or scuppers shall be provided where the roof perimeter extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. In other words, two independent methods are required to drain storm water off a roof that is enclosed with a parapet. Please review and clarify. Reference IBC Sections 1503.4, 1611, and UPC Appendix D1.1. Sheet A-4 1. Building perimeter wall elevation marks do not agree with what is shown on the plan. Please coordinate. Reference IBC Section 106.1.1. Sheet A-5 1. Please identify all required safety glazing. Reference IBC Section 2406.2. 2. The plans indicate three doors through the east wall. The elevation only shows two doors. Please review and coordinate. Reference IBC Section 106.1.1. Sheet E-1 1. Please provide a note on the drawing for suspended ceiling to comply with ASTM C635/C636 and CISCA-02, with seismic forces determined in accordance with the IBC for seismic design category C. Reference IBC Sections 803.8.1.1 and 1621.2.5.2.1. STRUCTURAL COMMENTS Sheet A-1 1. Please note that shear wall details are shown on four different sheets. Please coordinate and show only on one sheet. Reference IBC Section 106.1.1. Sheet A-2 1. Hangers from roof joists shall be in accordance with the manufacturer's details. Ramset screw upward into the bottom flange of a wood member is usually not an acceptable detail, due to real potential for pulling out of the bottom flange of a wood member that flexes up and down. Please review and coordinate. Reference IBC Section 106.1.1. 2. Similar general structural notes are shown on two different drawings. Please provide coordinated general structural notes on one drawing. Reference IBC Section 106.1.1. Sheet A-3 1. Please identify all required structural design criteria on the drawing. Reference IBC Sections 1603, and 1605. 2. Please provide printout for the derivation of seismic design parameters using the IBC seismic computer disc provided with each copy of the 2000 IBC. Identify site class and seismic design category. Reference IBC Sections 1615.1.1 and 1616. 3. Notwithstanding that wind lateral load may be higher than seismic load, structural detailing shall be that required for seismic conditions. Please provide calculation for total design base seismic shear. Reference IBC Section 1609.1.5. 4. Roof top screen loads and mechanical loads are not included in the design calculations for the roof beams and lintels. Please coordinate. Reference IBC Section 1607.8.2. 5. Please provide design calculations and construction details for the masonry screen wall that abuts the property line. Reference IBC Section 1604.4. 6. Please provide design calculations and construction details for the rooftop screen wall. Reference IBC Section 1604.4. 7. It is not clear to the reviewer, which interior walls are bearing walls and which are not. Interior walls, which are not bearing walls, shall be deleted from the structural framing plan. Reference IBC Section 106.1.1. 8. Please provide on the drawing the required location, roof opening framing and design weights for all mechanical units supported by the roof framing. Reference IBC Sections 1606.2 and 1607.8.2. 9. Allowable soil bearing pressure is identified as 2000 psi. Please review and correct. Reference IBC Section 106.1.1. 10. Please provide the special inspection documents required by the City of Tucson for concrete materials and structural masonry and soils special inspection. Reference IBC Sections 1704.1.1, 1704.4.1, 1704.5, and 1704.7. 11. Gypsum board shears walls shall not be used for the lateral support of masonry walls. Please coordinate. Reference IBC Section 2306.4.5, footnote a. 12. General note calls for wall footings to continue beyond the end of the wall. Please coordinate that requirement for wall footings located at the property line. Reference IBC Section 106.1.1. 13. Provide specifications for required structural masonry in compliance with IBC and ACI 530/530.1-1999. Reference IBC Section 2104.10. 14. The correct concrete design code standard is the ACI-318-1999. Please correct notes and provide correct designation for lap splices in concrete. Reference ACI-318, 12.15. 15. Please note that lap splices for reinforcing in masonry shall be determined as required by IBC Section 2107.2.3. Sheet D1 1. Please identify the dimension from grade to underside of treated wood sill. Non-treated sheathing shall not be located closer than 6 inches above earth grade. Reference IBC Section 2304.11. 2. Masonry walls shall have positive anchorage to the diaphragm. Please review and clarify. Reference IBC Section 1620.2.1. 3. Detail 12 shall be separated into two details to clearly show the structural construction requirements for ledgers on stud walls and the detail at lintels. Please clarify the number of jack studs and design calculation for maximum joist shear load. Reference IBC Section 1604.4. 4. Please clarify cleanout locations and slope of building sewer to the street. Reference UPC Section 707. Soils Report 1. The soils report identifies that the passive earth pressure shall only be considered valid for design if the ground adjacent to the foundation structure is essentially level for a distance of at least three times the total depth of the foundation. Although the classic soil wedge theory provides a convenient method to predict passive pressure, the actual failure spiral soil surface often necessitates increasing the horizontal level distance to achieve the full magnitude of passive pressure. Further, the allowable footing bearing pressure in the vicinity of a descending slope when loaded with an inclined load towards that slope is more complex than simply concluding a safe lateral distance equal to 3 times the depth of footing. So as not to misinterpret the intended conclusion, please identify the total limiting soil/footing design condition with a scale diagram showing passive soil spiral failure surface, unified soil classification for the design soil, coefficient of internal friction for the design soil, cohesion value, soil density, and soil grade surfaces along the boundary of passive soil and soil mechanics calculations to fully support the safe design bearing pressure and lateral passive soil and sliding conditions in the vicinity of a descending soil slope. Reference IBC Sections 1803, 1804, 1805, 1604.4, and 1610.2. PLUMBING COMMENTS Sheet P1 1. Please identify compliance with the 1994 UPC with State of Arizona amendments and the 1998 IECC. . Reference IBC Section 106.1.1. 2. Plumbing drains and sewers shall be noted to have ΒΌ inch per foot drainage gradient. Reference UPC Sections 708 and 718. 3. A maximum of three water closets are allowed on a 3-inch diameter sanitary drain. Please coordinate. Reference UPC Table 7-5. 4. Two hose bibs are called for on the schedule, but only one could be identified on the plan. Please coordinate. Reference IBC Section 106.1.1. 5. Please coordinate fixture units. Reference UPC Table 6-3 and Table 7-3. 6. Please identify location for future furnace units, total gas demand and total developed length for proper sizing of gas piping. Reference UPC Section 1217. MECHANICAL COMMENTS Sheet M1 1. Please coordinate location of mechanical units with other discipline plans. Reference IBC Section 106.1.1. 2. Please show vacuum line and proposed location of future air compressor. Reference IBC Section 106.1.1. ELECTRICAL COMMENTS Sheet E1 1. Please identify the lamp type and shielding requirements for compliance with the City of Tucson Outdoor Lighting Code. Reference IBC Section 106.1.1. 2. The proposed 3-phase 400-ampere service exceeds 225 amperes. The State Board thereby requires the electrical system to be under seal of a registered and licensed Arizona Electrical Engineer. Please comply. Reference Arizona, R4-30-302. 3. Please provide fault current analysis. Reference NEC Article 110-9. ENERGY CODE COMMENTS Sheet A-1 1. Please identify on the drawing, the U-value, SHGC required for all glazing and doors. Reference IECC Section 104.2. Sheet M1 1. Furnace BTUH of 200,000 for proposed current office space of 2145 s.f appears to be excessive. Please review and provide appropriate analysis. Reference IECC Section 703.2. 2. Please provide note to identify the required amount of duct insulation and the required sealing of ducts. Reference IECC Section 703.8. 3. Building envelope thermal calculation criteria is in error. Please correct. Reference IECC Table 302.1. Sheet E-1 1. Please note that each area that is required to have a manual control shall also allow the occupant to uniformly reduce the connected lighting load by at least 50%. Please review and show compliance. Reference IECC Section 705. ACCESSIBILITY COMMENTS: Sheet A-1 1. Please clarify toilet room grab bar length behind water closet. Water closet for ADAAG shall be located 18 inches off the sidewall. Reference ADAAG Section 4.16. |
| 03/27/2003 | EROSE1 | NPPO | REVIEW | Needs Review | |
| 03/27/2003 | EROSE1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/02/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |