Permit Number: T03CM01266
Parcel: 12704284A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01266
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2003 ELAINE ROSE ZONING REVIEW Needs Review
03/28/2003 EROSE1 WATER REVIEW Needs Review
03/28/2003 EROSE1 WWM REVIEW Needs Review
03/28/2003 EROSE1 FLOODPLAIN REVIEW Needs Review
03/28/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS

1. Please coordinate comments for this tenant space with the comments for the shell building space under permit application T03CM01267.


ARCHITECTURAL COMMENTS
Sheet CVR

1. Please identify the tenant occupant load. Reference IBC Section 1003.2.2.

2. Please identify the construction type. Reference IBC Section 601.

Sheet A-1

1. Please declare the overall building plan dimensions for the tenant space. Reference IBC Section 501.1.

2. Please identify the hard nonabsorbent finish required in toilet rooms. Reference IBC Section 1209.


STRUCTURAL COMMENTS

1. Hangers from roof joists shall be in accordance with the manufacturer's details. Ramset screw upward into the bottom flange of a wood member is usually not an acceptable detail, due to real potential for pulling out of the bottom flange of a wood member that flexes up and down. Please review and coordinate. Reference IBC Section 106.1.1.

2. Provide calculations evidencing that the roof joists are adequate to safely support the weight of the intended HVAC units plus 20%. Reference IBC Section 1607.8.2.


PLUMBING COMMENTS
Sheet P-1

1. Please clarify whether or not the building tenant is provided with a gas meter that is separate from the other tenant space. Reference IBC Section 106.1.

2. Please identify the location where the three-inch building drain transitions to the four-inch building sewer. Reference UPC Section 715.

3. Please identify required ΒΌ per foot slope for building drains. Reference UPC Sections 708 and 718.

4. Please coordinate required fixture units for water supply and sanitary drains. Reference UPC Table 6-3, Table 7-3.


MECHANICAL COMMENTS:
Sheet P2

1. Provide specification rating for the proposed ait compressor and vacuum pump systems including horsepower and full load electrical power. Reference IMC Section 1011, and NEC Article 220-14.


ELECTRICAL COMMENTS:
Sheet E2

1. The proposed three-phased 400-ampere service exceeds 225 amperes. The State Board thereby requires the electrical system to be under seal of a registered and licensed Arizona Electrical Engineer. Please comply. Reference Arizona, Section R4-30-302.

2. Please provide fault current analysis. Reference NEC Article 110-9.


ENERGY CODE COMMENTS:
Sheet CVR

1. Please identify compliance with the 1998 IECC. Reference IBC Section 106.1.1.

2. Please coordinate building thermal design criteria with IECC Table 302.1 as adopted by the City of Tucson.



Sheet P1

1. The furnace heat supply of 220,000 BTUH for the tenant space of 1624 square feet appears to be excessive. Please clarify thermal sizing of gas furnace. Reference IECC Section 703.2.


ACCESSIBILITY COMMENTS:

1. The accessibility portion has been reviewed and accepted.
03/28/2003 EROSE1 NPPO REVIEW Needs Review
03/28/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed