06/18/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The submitted detail for the protection of the door grille in the laundry room applies to a wall, not a door. If you are unable to find a listed combination fire/smoke dampers for a door grille, use an alternate method of obtaining make-up air for the laundry room. Reference Section 715, IBC.
06/18/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The revised water calculations do not appear to apply to either the current project or the complete building. Show how the existing 2" water service can support the total water demand for the building. Note: the use of a 1-1/2" meter for 51 GPM exceeds the maximum allowed velocity. Reference Sections 610.1 and A 6.1, UPC 1994.