Permit Number: T03CM01256
Parcel: 10409002D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01256
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
05/21/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. Reference Section 607.3, IMC 2000.
2. Provide approved combination fire/smoke dampers for protection of door grille in laundry room. Reference Section 715, IBC.
3. The exhaust fan in the expanded men's restroom is called out as EF-4 on the plans. Is this the same fan as the second EF-3 on the Exhaust Fan Schedule?
4. Keynote 23 specifies termination of a condensate drain at the tailpiece of a lavatory but keynote 22 points out the termination of the condensate drains on the drawing. Please resolve.
5. The expansion of the men's restroom has resulted in a return grille for an existing rooftop heat pump being located in the restroom. Please relocate. Reference Table 403-3, footnote b, IMC 2000.
05/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised water calculations indicate a total fixture count of 113 fixture units in the completed tenant improvement. Show how the existing 2" water service to the whole building can support the increased water demand. Reference Section 610.1, UPC 1994.
06/05/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2003 TAMI ACHONG OUT TO CUSTOMER Completed
06/05/2003 ANGIE SHOFFSTALL REJECT SHELF Completed