Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM01256
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/12/2003 | JAMES TATE | FLOODPLAIN | REVIEW | Approved | |
| 03/12/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 03/18/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/21/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/21/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide end of line cleanout at shower. Reference Section 707.4, UPC 1994. |
| 03/21/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Relocate duct smoke detectors to the return ducts. Reference Section 606.2.1, IMC 2000. 2. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive walls (storage rooms and laundry). Reference Section 715, IBC. 3. Confirm existing exhaust fans in restrooms exhaust at least 75 CFM per water closet or urinal. Reference Table 403.3, IMC 2000. 4. Recalculate outdoor air requirements for project using Table 403.3, IMC 2000. 5. Confirm that adequate makeup air is supplied to the laundry. Reference Section 504.5, IMC 2000. 6. Provide a detail showing the conformance of the dryer exhaust ducts to the requirements of Section 504, IMC 2000. 7. Clarify method of termination of condensate drain at laundry sink. Connection to the tailpiece of a sink is not approved, only to the tailpiece of a lavatory. Reference Section 807.2, UPC 1994 and Section 307.2.1, IMC 2000 local amendments. |
| 04/15/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. indicate the existing service lateral conductor sizes. 2.Panel "A" is too small for the applied load. |
| 04/24/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Indicate and locate on plans required panic and exit hardware. Reference section 1003.3.1.9 2. Two means of egress required from main area. Reference table 1004.2.1 IBC. Note: area also being served by conference room. Revise plan 3. Womens room accessible toilet compartment does not meet the clearance requirements of section 604.8 ANSI A117.1. Revise plan 4. Doors part of accessible routes must meet the maneuvering clearance requirements of section 404.2.4 ANSI A117.1. Revise plans 5. An additional mens water closet required per table 2902.1 IBC. Revise plan |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/24/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |