Permit Number: T03CM01256
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM01256
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2003 JIM EGAN FIRE REVIEW Approved
03/12/2003 JAMES TATE FLOODPLAIN REVIEW Approved
03/12/2003 DAN CASTRO ZONING REVIEW Approved
03/18/2003 GERRY KOZIOL WWM REVIEW Approved
03/21/2003 ROBERT SHERRY WATER REVIEW Approved
03/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide end of line cleanout at shower. Reference Section 707.4, UPC 1994.
03/21/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Relocate duct smoke detectors to the return ducts. Reference Section 606.2.1, IMC 2000.
2. Provide approved combination fire/smoke dampers for protection of ducts and penetrations of fire resistive walls (storage rooms and laundry). Reference Section 715, IBC.
3. Confirm existing exhaust fans in restrooms exhaust at least 75 CFM per water closet or urinal. Reference Table 403.3, IMC 2000.
4. Recalculate outdoor air requirements for project using Table 403.3, IMC 2000.
5. Confirm that adequate makeup air is supplied to the laundry. Reference Section 504.5, IMC 2000.
6. Provide a detail showing the conformance of the dryer exhaust ducts to the requirements of Section 504, IMC 2000.
7. Clarify method of termination of condensate drain at laundry sink. Connection to the tailpiece of a sink is not approved, only to the tailpiece of a lavatory. Reference Section 807.2, UPC 1994 and Section 307.2.1, IMC 2000 local amendments.
04/15/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. indicate the existing service lateral conductor sizes. 2.Panel "A" is too small for the applied load.
04/24/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Indicate and locate on plans required panic and exit hardware. Reference section 1003.3.1.9
2. Two means of egress required from main area. Reference table 1004.2.1 IBC. Note: area also being served by conference room. Revise plan
3. Womens room accessible toilet compartment does not meet the clearance requirements of section 604.8 ANSI A117.1. Revise plan
4. Doors part of accessible routes must meet the maneuvering clearance requirements of section 404.2.4 ANSI A117.1. Revise plans
5. An additional mens water closet required per table 2902.1 IBC. Revise plan

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
04/24/2003 ANGIE SHOFFSTALL REJECT SHELF Completed