Permit Number: T03CM01247
Parcel: 123052210

Address:
2209 N TUCSON BL

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM01247
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2003 JIM TATE ENGINEERING REVIEW Approved Flood Use Permit No. T03OT00540
06/30/2003 ELAINE ROSE ZONING REVIEW Needs Review
06/30/2003 EROSE1 WWM REVIEW Needs Review
06/30/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Provide drawings drawn to scale to verify code compliance of dimensional requirements.

Sheet 3
1. Please specify moisture resistive surface for shower space to a height of 6 feet above finished floor. Ref. R307.

2. Provide construction dimensions for framing. As an example, where will the north wall of the new bedroom 2 be constructed?

3. Provide hardwired, interconnected smoke alarms with battery back up for all sleeping rooms and the areas outside and in the immediate vicinity of the sleeping areas. Ref. R317.

STRUCTURAL COMMENTS
Sheet 5
1. Specify joists. If these are Truss Joist Macmillan TJI's, specify the series number to verify joist adequacy.

PLUMBING COMMENTS
Sheet 7
1. Provide venting for water heater in accordance with UPC 512.

2. Show complete drain, waste and vent provisions for shower and laundry. Ref. UPC Ch. 7.

MECHANICAL COMMENTS
General
1. Demonstrate provisions for maintaining a temperature of 68 degrees at 3 feet above the finished floor elevation. Ref. R303.6.

ELECTRICAL COMMENTS
Sheet 3
1. Please verify the adequacy of the existing electrical service. Show the existing service size and load. Provide the panel schedule, new load calculation and indicate the circuits to be used.

2. Receptacles must be located on the scaled drawings to be provided in such a manner that compliance for outlet spacing may be determined. Ref. E 3801.2.

ENERGY COMMENTS
Sheet 4
1. Please note R-values for batt insulation.
06/30/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2003 ELAINE ROSE OUT TO CUSTOMER Completed