Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM01199
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS General 1. Please specify wall heights, top of ledger and top of beam dimensions. 2. Provide dimensions for the location of the roof hatch. 3. Show the landing at the exterior side of the equipment room door. 4. Please specify / detail the construction of the equipment room roof. 5. Reference Detail 4/A14 for the construction of the scuttle and ladder. STRUCTURAL COMMENTS General 1. Please specify foundation and footing details / dimensions for the equipment room. 2. Connections at the roof hatch opening were not specified for the perpendicular attachment of the TJI members and 2x6 to the (2) 2x12 headers or the (2) 2x12 headers to the CMU wall and truss. Please clarify. ELECTRICAL COMMENTS General 1. Please clarify receptacles and lighting (interior and exterior) to be included in the scope of the equipment room construction. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/22/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |