05/22/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. With 111 amps on the Panel, the 100A CB should be replaced with one of higher capacity.
2. Fixture "AA" on Plan appears to be on both Circuits 9,11 and 13,15. Please clarify.
3. Please clarify 34" conduit on plan view.
4. Please clarify 206A meter on plan view.
5. Please specify depth of conduit fill.