Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM01117
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. With 111 amps on the Panel, the 100A CB should be replaced with one of higher capacity. 2. Fixture "AA" on Plan appears to be on both Circuits 9,11 and 13,15. Please clarify. 3. Please clarify 34" conduit on plan view. 4. Please clarify 206A meter on plan view. 5. Please specify depth of conduit fill. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 05/23/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |