Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM01117
Parcel: 10712215B

Address:
21 W LAGUNA ST

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM01117
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. With 111 amps on the Panel, the 100A CB should be replaced with one of higher capacity.
2. Fixture "AA" on Plan appears to be on both Circuits 9,11 and 13,15. Please clarify.
3. Please clarify 34" conduit on plan view.
4. Please clarify 206A meter on plan view.
5. Please specify depth of conduit fill.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
05/23/2003 ANGIE SHOFFSTALL REJECT SHELF Completed