The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01068
Parcel: 133153330

Address:
1889 N KOLB RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM01068
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2003 EROSE1 FIRE REVIEW Needs Review
03/10/2003 EROSE1 WATER REVIEW Needs Review
03/10/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:
1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, and 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.

ARCHITECTURAL COMMENTS:
1. The Architectural Plans have been reviewed and approved.

STRUCTURAL COMMENTS:
1. The Structural Plan sheets are missing from both sets of plans. Please provide for completion of plan review. Reference IBC Section 106.1.1.

PLUMBING COMMENTS:
1. The limited, rough Plumbing Plan has been reviewed and accepted.

MECHANICAL COMMENTS:
1. Not applicable to this Shell-Only building.

ELECTRICAL COMMENTS:
1. The partial Electrical Plans have been reviewed and accepted.

ENERGY CODE COMMENTS:
1. The Building Envelope details and Energy Code calcs have been reviewed and accepted, subject to submitting the Mechanical and Lighting Energy interior and exterior calcs for approval with the Tenant Improvement plans. Reference IBC Section 106.1.1.

ACCESSIBILITY COMMENTS:

1. Parking and access to the building has been reviewed and accepted. However, accessibility to the tenant space(s) and toilets shall be reviewed with the Tenant Improvement plans. Reference ICC/ANSI 117.1.
03/10/2003 EROSE1 FLOODPLAIN REVIEW Needs Review
03/10/2003 ELAINE ROSE ZONING REVIEW Needs Review
03/10/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed