Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM01031
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plans and the exhaust fan schedule. Reference Section 302.3, Uniform Administrative Code 1997. 2. At their maximum flow, VAV03-2 and VAV03-3 are capable of supplying more air to the spaces they serve than is exhausted. Please revise to comply with Section 403.2.1(3), IMC 2000. |
| 05/27/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide upper terminal cleanout on horizontal drainage pipe from WC-3 in room 102. Reference Section 707.4, UPC 1994. 2. Provide upper terminal cleanouts on horizontal drainage pipes from water closets in room 106. Reference Section 707.4, UPC 1994. 3. Provide upper terminal cleanout on horizontal drainage pipe from lavatories in room 106. Reference Section 707.4, UPC 1994. 4. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. 5. Show routing and termination of T&P relief piping from WH-2. Reference Section 608.5, UPC 1994. 6. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 1994. |
| 06/20/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/27/2003 | GERRY KOZIOL | WWM | REVIEW | Needs Review | |
| 06/27/2003 | DAVE MANN | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/30/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 06/27/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |