Permit Number: T03CM01031
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM01031
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2003 JIM EGAN FIRE REVIEW Approved
03/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/06/2003 ROBERT SHERRY WATER REVIEW Approved
03/11/2003 GERRY KOZIOL WWM REVIEW Approved
03/19/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/07/2003 DAVE MANN BUILDING-COMMERCIAL REVIEW Approv-Cond Clarify if outdoor areas are part of permit.
04/11/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheets E0.2 & E6.1, Line Diagrams
1. On Sheet E0.2 Panel FCL is ETR, and powering new Panel FCR. On Sheet E6.1, Panel FCL is shown as new, as are its feeder and fused disconnect. Please clarify.
2. Also note that Panel FCL is ETR on Sheet E2.3, but shown as new on E2.1 and E6.1. Please clarify.
3. Provide load calculation for MSB-4.

Sheets E0.1 & E0.2, Panel Schedules
1. Panel Schedule for new Panel FCL is on both of the above sheets. On Sheet E2.1 the transformer load has not been included. Please clarify.
2. Panel Schedule FCL does not include the 125/3 circuits to the Dimming Panel. Please include.
3. Please provide corrected load calculations for Panel FCL.
4. Interrupting capacity for Panel FCR is undefined. Please define.

Sheet E2.3, Fountain
1. Provide specifications for Fountain Control Panel and Fountain Pump Motors.
2. Provide overload protection, disconnect, ground fault & short circuit protection for motors.
3. Demonstrate that electrical equipment that depends on submersion for safe operation is protected against overheating per NEC 680-51 (d).
4. Provide Ground Fault Circuit Interrupter per NEC 680-51 (a).
5. Provide fixture cut sheets for fountain lights. Demonstrate that the voltage of such fixtures does not exceed 150V, per NEC 680-50 (b).
6. Specify installation per NEC 680-51 (c), (e), (f), & (g).
7. Specify material and workmanship for Junction Box per NEC 680-52 (b).
8. Specify grounding and bonding per NEC 680-53, 680-54, and 680-55. Call for an isolated ground from fountain equipment to the panelboard supplying such equipment.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2003 CINDY AGUILAR OUT TO CUSTOMER Completed