Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM01020
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2003 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | FUP NO. T02OT00168 |
| 03/05/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/07/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/19/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/19/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide clarification of existing versus new plumbing fixtures. |
| 03/19/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide secondary drains or auxiliary drain pans for all fan coil units. Reference Section 307.2.3, IMC 2000. 2. Resolve disparity between the Heat Pump / Fan Coil Schedule and the plans for the quantities of outside air to be supplied. |
| 03/20/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 04/09/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/22/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Storage area requires a one-hour fire barrier per section 302.1.1. Provide detail and listing of the required fire barrier. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/22/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |