Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM01013
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | City of Tucson No. T03CM01013 GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q The calculation on Page 27 indicates a masonry lintel for an 8'-8" opening. However on the plans there is only one opening that is of this size and it has a wide flange lintel, for which a calculation has not been provided. Please provide the calculation for the wide flange lintel. This previous comment has been partially addressed. The calculation on Page 27 is for another opening that is over 8'-0" wide (I was incorrect that there was only one opening this wide). Detail 7 on Sheet S3.1 is for a wide flange beam at a new opening in and existing masonry wall. Where is the calculation for this beam? Please provide. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q There are no electrical comments to be addressed. |
| 04/03/2003 | EROSE1 | NPPO | REVIEW | Needs Review | |
| 04/03/2003 | EROSE1 | FIRE | REVIEW | Needs Review | |
| 04/03/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 04/03/2003 | EROSE1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/03/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |