02/25/2003 JIM EGAN FIRE REVIEW Approved
03/06/2003 DAVID RIVERA HANDICAP-SITE REVIEW Denied see zoning comments
03/06/2003 DAVID RIVERA ZONING REVIEW Denied FROM: David Rivera FOR: Patricia Gehlen
Senior Planner Principal Planner

PROJECT:


USE:
T03CM00953
965 W. 24th Street
Santa Cruz Harvest Center
Religious Use - New Church DD "12"
Residential Use - Existing residence DD "G" Transmittal date:

1st Review March 5, 2003

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. In order to allow the two proposed uses on this parcel of land a total of 27,000 square feet is required for the minimum lot size. This parcel of land is only 16,500 square feet, which sufficient for the residential use only. In order to allow the uses as proposed the property must be rezoned to a minimum of R-3. This plan has been reviewed under the assumption that the owner will either apply for variances or will rezone the property.
DS 2-02.2.1.A.5

2. There were no building elevation drawings in the site plan packet to verify the building height or design. Please indicate on the plan if the height of the building is to the top of parapet, wall, gable roof etc or provide copies of the building elevations. (Required in order to verify heights and required building setbacks.) The required building setback along the south side of the building is based on the greatest of ten (10) feet or three quarters (3/4) the height of the structure. Revise the 1.2 note. If applicable indicate if there is a proposed steeple or tower and if so indicate the overall height.
DS 2-02.2.1.A.7

3. Based on the proposed 1500 square feet for the sanctuary, the number of vehicle parking spaces required for the Church use is 30 spaces plus the two (2) spaces for the residence. Per the plan 16 vehicle parking spaces have been provided. A board of adjustment variance to the required number of parking spaces will be required. LUC 3.3.4 Religious and residential use. Also please dimension the bicycle parking facility and indicate the type lighting that will be provided.
DS 2-02.2.1.A.9

4. An access ramp next to the handicap aisle must be provided. Add the ramp and indicate the required slope 12:1. If needed provide a dimensioned detail drawing that indicates the where the ramp will be provided and the direction of slope.
DS 2-02.2.1.A.12

5. The location of the refuse container must be shown on the plan to insure that the container will not interfere with other LUC requirements such as pedestrian sidewalks, vehicle parking, landscaping etc.
DS 2-02.2.1.A.32

6. In order for the this project to continue as proposed the parcel must be rezoned to R-3 minimum or must apply for variances related to required lot area, lot coverage, and required vehicle parking. Please respond with the next site plan submittal what the owner proposes to do. If additional comments related to zoning variances are needed I will provide the comments as required based on the revised plan.

7. See landscape reviewer comments. If changes are made to the site plan please insure that both the site plan and landscape plan match.



If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and landscape plan and requested documents.
03/19/2003 DOUG WILLIAMS SANITATION REVIEW Denied SUBJECT: Santa Cruz Harvest Center
REVIEWER: Doug Williams
DATE: 20 March 2003
ACTIVITY NUMBER: T03CM00953

SUMMARY: Engineering Division has reviewed the site plan received on February 25, 2003. Approval of the Site Plan is not recommended at this time. The following comments are offered:

SITE PLAN COMMENTS:

1. The proposed drainage patterns and finish grades at the southeastern portion of the site appear to be concentrating drainage discharge in a fashion that does not appear to match existing conditions. Overall patterns in this area are to the northeast. Revise proposed patterns accordingly, maintaining existing drainage patterns (DS 2-02.2.1.16; LUC 3.7.4);
2. Provide estimated cut and fill quantities (DS 2-02.2.1.17);
3. Depict the refuse container size, location and access thereto, fully dimensioned (DS 2-02.2.1.32);
4. Address roof drainage direction(s) and associated sidewalk scuppers for conveyance under sidewalk areas (DS 2-08.4.1 E and 3-01.4.4 F)
5. Depict and label concrete headers (PC/COT SD 213) at the curb returns in the 24th Street right of way. As noted in keynote 4, a separate right of way permit will be required (DS 3-01.3.2 D);
6. The maximum driveway width allowed in residential districts is 20 feet (Tucson Code, Section 25-38).

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.



Doug Williams
Engineering Division
Development Services Department
03/19/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Santa Cruz Harvest Center
REVIEWER: Doug Williams
DATE: 20 March 2003
ACTIVITY NUMBER: T03CM00953

SUMMARY: Engineering Division has reviewed the site plan received on February 25, 2003. Approval of the Site Plan is not recommended at this time. The following comments are offered:

SITE PLAN COMMENTS:

1. The proposed drainage patterns and finish grades at the southeastern portion of the site appear to be concentrating drainage discharge in a fashion that does not appear to match existing conditions. Overall patterns in this area are to the northeast. Revise proposed patterns accordingly, maintaining existing drainage patterns (DS 2-02.2.1.16; LUC 3.7.4);
2. Provide estimated cut and fill quantities (DS 2-02.2.1.17);
3. Depict the refuse container size, location and access thereto, fully dimensioned (DS 2-02.2.1.32);
4. Address roof drainage direction(s) and associated sidewalk scuppers for conveyance under sidewalk areas (DS 2-08.4.1 E and 3-01.4.4 F)
5. Depict and label concrete headers (PC/COT SD 213) at the curb returns in the 24th Street right of way. As noted in keynote 4, a separate right of way permit will be required (DS 3-01.3.2 D);
6. The maximum driveway width allowed in residential districts is 20 feet (Tucson Code, Section 25-38).

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.



Doug Williams
Engineering Division
Development Services Department
03/19/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Denied SUBJECT: Santa Cruz Harvest Center
REVIEWER: Doug Williams
DATE: 20 March 2003
ACTIVITY NUMBER: T03CM00953

SUMMARY: Engineering Division has reviewed the site plan received on February 25, 2003. Approval of the Site Plan is not recommended at this time. The following comments are offered:

SITE PLAN COMMENTS:

1. The proposed drainage patterns and finish grades at the southeastern portion of the site appear to be concentrating drainage discharge in a fashion that does not appear to match existing conditions. Overall patterns in this area are to the northeast. Revise proposed patterns accordingly, maintaining existing drainage patterns (DS 2-02.2.1.16; LUC 3.7.4);
2. Provide estimated cut and fill quantities (DS 2-02.2.1.17);
3. Depict the refuse container size, location and access thereto, fully dimensioned (DS 2-02.2.1.32);
4. Address roof drainage direction(s) and associated sidewalk scuppers for conveyance under sidewalk areas (DS 2-08.4.1 E and 3-01.4.4 F)
5. Depict and label concrete headers (PC/COT SD 213) at the curb returns in the 24th Street right of way. As noted in keynote 4, a separate right of way permit will be required (DS 3-01.3.2 D);
6. The maximum driveway width allowed in residential districts is 20 feet (Tucson Code, Section 25-38).

If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.



Doug Williams
Engineering Division
Development Services Department
03/20/2003 JOE LINVILLE NPPO REVIEW Approved Exception. No viable protected plants on site.
03/21/2003 JOE LINVILLE LANDSCAPE REVIEW Denied Five foot high screens are required to screen the site from adjacent streets. LUC 3.7.3, Table 3.7.2-I. Revise the site and landscape plans as necessary.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2003 LISA LESNY OUT TO CUSTOMER Completed