Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM00918
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/26/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
03/04/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide building sewer cleanouts at intervals not exceeding 100 feet. Reference Section 719.1, UPC. 2. Indicate maximum installed height of water heater on plans. Reference Section 511.2, UPC. |
03/04/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide either return or exhaust air capability to kitchen addition. Reference Section 403.1, IMC. 2. Provide a minimum of 10-feet clearance between the outside air intake on AC-19 and the sanitary vent. Reference Section 401.5.1, IMC. Please show the locations of the rooftop air conditioners in consistent locations on each sheet. 3. Provide duct smoke detectors for return air systems with a design capacity greater than 2000 CFM (or an area smoke detection system). Reference Section 606.2, IMC. 4. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC. |
03/04/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/12/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/18/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Passed | |
03/21/2003 | JAMES TATE | FLOODPLAIN | REVIEW | Approved | |
04/08/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/15/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/15/2003 | LISA LESNY | REJECT SHELF | Completed |