Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM00918
Parcel: 113111010

Address:
1701 E SENECA ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM00918
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2003 JIM EGAN FIRE REVIEW Approved
03/04/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide building sewer cleanouts at intervals not exceeding 100 feet. Reference Section 719.1, UPC.
2. Indicate maximum installed height of water heater on plans. Reference Section 511.2, UPC.
03/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide either return or exhaust air capability to kitchen addition. Reference Section 403.1, IMC.
2. Provide a minimum of 10-feet clearance between the outside air intake on AC-19 and the sanitary vent. Reference Section 401.5.1, IMC. Please show the locations of the rooftop air conditioners in consistent locations on each sheet.
3. Provide duct smoke detectors for return air systems with a design capacity greater than 2000 CFM (or an area smoke detection system). Reference Section 606.2, IMC.
4. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
03/04/2003 ROBERT SHERRY WATER REVIEW Approved
03/12/2003 GERRY KOZIOL WWM REVIEW Approved
03/18/2003 PATRICIA GEHLEN ZONING REVIEW Passed
03/21/2003 JAMES TATE FLOODPLAIN REVIEW Approved
04/08/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/15/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2003 LISA LESNY REJECT SHELF Completed