Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM00900
Parcel: 12701008A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00900
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The provided calculations do not demonstrate compliance to Section 403, IMC.
a. Indicate the occupant classification used to determine the required amount of outside air for each space. If several spaces are served by a common source of ventilation, determine the total amount of supply air to be delivered using the methods presented in Section 403.3.2, IMC.
b. Provide outside air calculations for the mezzanine offices as well as the Team Office (113) and the Control Room (114).
c. The entry, served by RTU-19, should be classified as "Retail…: basement and street". Reference Table 403-3, IMC.
d. The Food Service area should be classified as "Food & Beverage: cafeteria, fast food". Reference Table 403-3, IMC.
e. Existing roof top units being modified to supply air to new spaces are to be included in the calculations.
05/15/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied General Comment:

The 2000 edition of the UPC has not been incorporated into the Arizona Uniform Plumbing Code; the 1994 edition of the UPC is the accepted code. Reference Section R4-48-102, Arizona Uniform Plumbing Code.

Plumbing Comments:

1. Use the fixture units shown in tables 6-3 and A-2 for water supply system calculations. Include the pressure drops associated with the water meter and reduced pressure backflow preventer assembly at demand flow when calculating the permissible friction loss in accordance with Appendix A, UPC with AZ State amendments.
2. Provide cleanout on each vent serving the floor drains located between columns D and F, and columns 2 and 5. Reference Section 910.6, UPC with AZ State amendments.
3. The traps as well as the waste lines for the floor drains located between columns D and F, and columns 2 and 5 shall be 2 pipe sizes larger than required by Table 7-3, UPC with AZ State amendments. Reference Section 910.4, UPC with AZ State amendments.
4. Floor drain FD-4, as shown in Detail 17/M10, does not meet the requirements of section 410-1, UPC with AZ State amendments.
5. Provide trap primers for FD-4 floor drains. Reference Sections 1007.0 and 1007.1, UPC with AZ State amendments.
6. Confirm that the three-compartment sink (FS0042) complies with Section 801.2, UPC with AZ State amendments.
7. The seven cleanouts provided for the horizontal drain lines in the food service area are not located at the upper terminals of the horizontal drain lines. Reference Section 707.4, UPC with AZ State amendments.
8. The cleanout provided for the drain line serving F4 is not located at the upper terminal of the horizontal drain line. Reference Section 707.4, UPC with AZ State amendments.
9. Show size and routing of overflow drains and piping. Reference Appendix D 1.1 (d), UPC with AZ State amendments.
10. The floor drain, FD-1, near the 3-compartment sink does not comply with Section 1011.3, UPC with AZ State amendments. The cleanout provided for this fixture is not located at the upper terminal of the horizontal drain line. Reference Section 707.4, UPC with AZ State amendments.
06/03/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
06/09/2003 GERRY KOZIOL WWM REVIEW Approved
06/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2003 TAMI ACHONG REJECT SHELF Completed
06/17/2003 DELMA ROBEY OUT TO CUSTOMER Completed