Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM00890
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
04/15/2003 | DAVE MANN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/15/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
04/23/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the number of fixtures on the Fixture Connection Schedule to agree with the plumbing plans. 2. Correct the water and waste fixture units on the Fixture Connection Schedule to the values shown on Table A-2 and Table 7-3, UPC 1994. The water fixture units shall be for public use. 3. Based on the calculations shown on the drawing, the DCW line to the restrooms is undersized. Please correct. 4. The trap arm for the lavatory, P-1, is noted as 2" on the Fixture Connection Schedule but 1-1/4" on the plans. A 1-1/4" trap arm does not comply with Section 1002.4, UPC 1994. |
04/23/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide details for the support of the Type I exhaust hood. Reference Section 506, IMC 2000. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/28/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |