Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM00890
Parcel: 12308007C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00890
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2003 JIM EGAN FIRE REVIEW Approved
04/15/2003 DAVE MANN BUILDING-COMMERCIAL REVIEW Approved
04/15/2003 PATRICIA GEHLEN ZONING REVIEW Approved
04/23/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the number of fixtures on the Fixture Connection Schedule to agree with the plumbing plans.
2. Correct the water and waste fixture units on the Fixture Connection Schedule to the values shown on Table A-2 and Table 7-3, UPC 1994. The water fixture units shall be for public use.
3. Based on the calculations shown on the drawing, the DCW line to the restrooms is undersized. Please correct.
4. The trap arm for the lavatory, P-1, is noted as 2" on the Fixture Connection Schedule but 1-1/4" on the plans. A 1-1/4" trap arm does not comply with Section 1002.4, UPC 1994.
04/23/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide details for the support of the Type I exhaust hood. Reference Section 506, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed