Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM00890
Parcel: 12308007C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM00890
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2003 JIM EGAN FIRE REVIEW Denied Minimum exit separaton distance shall conform to 2000 IBC Sec.1004.2.2.1 (Exception 2).
02/28/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
3/04/2003
Prior to doing a zoning review, a copy of the last approved site plan and parking calculations must be included in the submittal package. Please provide with the resubmittal of these plans.
03/04/2003 GERRY KOZIOL WWM REVIEW Approved
03/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide balancing data for existing exhaust fan in Women's Restroom. Reference Section 403.3, IMC 2000.
2. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
3. Provide calculations to show that the Type I kitchen hood is handling the proper exhaust volume. Reference Section 507.13, IMC 2000.
4. Provide details for the installation of a Type I exhaust system, including duct materials and construction, duct and hood supports, and duct enclosure construction. Reference Section 506, IMC 2000.
5. Provide details of Type I hood to demonstrate compliance to Section 507, IMC 2000.
03/06/2003 ROBERT SHERRY WATER REVIEW Approved
03/06/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show both existing and new gas piping on plans and in calculations to demonstrate compliance to Section 1217, UPC 1994.
2. Show location of listed automatic shutoff valve on gas piping schematic. Reference Section 302.3, Uniform Administrative Code 1994.
3. Provide complete plumbing plan, including water isometric and waste and vent isometric. Reference Section 302.3, Uniform Administrative Code 1994.
4. Show routing and termination of condensate drains from existing roof top air conditioners. Reference Sections 307.2.1 and 307.2.2, IMC (2000).
5. Show routing and termination of drains from makeup air unit. Reference Section 807.1, UPC 1994.
6. Clarify discrepancy between plans and keynote 24: is P-7 to have an indirect or direct waste connection?
7. If P-7 is to have an indirect waste connection, provide a detail showing compliance of indirect waste lines from P-7 with Section 803.0, UPC 1994.
8. Relocate floor sink shown in closet. Reference Section 804.1, UPC 1994.
9. Relocate floor sink under beverage dispenser and floor sink under icemaker to be readily accessible for inspection and cleaning. Reference Section 804.1, UPC 1994.
10. Show size, routing, and termination of condensate waste from refrigeration equipment on plans. Reference Sections 307.2.1 and 307.2.2, IMC (2000).
11. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
12. Provide detail of water heater installation, including excess pressure relief, expansion tank, and valves. Reference Section 302.3, Uniform Administrative Code 1994.
03/26/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/10/2003 DAVE MANN BUILDING-COMMERCIAL REVIEW Denied See Fire comment. Exits to be 1/2 the diagonal of area apart.
04/10/2003 DAVE MANN BUILDING-COMMERCIAL REVIEW Denied Provide detail of glass topped wall 8 on Sheet A-3. Provide connections to existing construction.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed