Permit Number: T03CM00881
Parcel: 12214007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM00881
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2003 JIM EGAN FIRE REVIEW Approved
02/21/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
2/24/2003
Please provide copies of the zoning stamped approved site plan with resubmittal of these plans.
03/03/2003 GERRY KOZIOL WWM REVIEW Approved
03/04/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate size, route, and termination of condensate drains from a/c units. Reference Section 307.2, IMC.
2. Show size, route, and all loads on gas piping. Reference Section 302.3, 1994 Uniform Administrative Code.
3. Show all cleanouts on waste and vent riser diagram. Reference Section 302.3, 1994 Uniform Administrative Code.
4. Resolve conflicting termination points for the P/T relief pipe on the plumbing plan and the water heater detail (3/P1). Reference Section 608.5, UPC.
5. Indicate maximum installed height of water heater on plans. Reference Section 511.2, UPC.
03/04/2003 ROBERT SHERRY WATER REVIEW Approved
03/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations. Reference Section 403.2, IMC.
03/12/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Exterior wall adjacent to property line is required to be of one-hour fire resistance construction. Reference Table 602 IBC. Revise code data and provide note: masonry expansion joints to be fire caulked
2. Include required panic hardware in door schedule. Note exit doors to the outside from classrooms are required exits per city code amendment to section 903.2.2 IBC.
3. Provide exit signage and illumination per section 1003.2.10 IBC
4. Landings are required at doors. Reference section 1003.3.1.5 IBC. Revise plan
5. Please clarify if door closers are to be used. If they are, provide required clearances for door approach. Reference figure 404.2.4.1ANSI A117.1
6. Indicate method of attachment of brick veneer. If anchoring method is used, provide typical cross section.
03/19/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2003 TAMI ACHONG OUT TO CUSTOMER Completed