Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM00881
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/21/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 2/24/2003 Please provide copies of the zoning stamped approved site plan with resubmittal of these plans. |
| 03/03/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/04/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Indicate size, route, and termination of condensate drains from a/c units. Reference Section 307.2, IMC. 2. Show size, route, and all loads on gas piping. Reference Section 302.3, 1994 Uniform Administrative Code. 3. Show all cleanouts on waste and vent riser diagram. Reference Section 302.3, 1994 Uniform Administrative Code. 4. Resolve conflicting termination points for the P/T relief pipe on the plumbing plan and the water heater detail (3/P1). Reference Section 608.5, UPC. 5. Indicate maximum installed height of water heater on plans. Reference Section 511.2, UPC. |
| 03/04/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/04/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation calculations. Reference Section 403.2, IMC. |
| 03/12/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Exterior wall adjacent to property line is required to be of one-hour fire resistance construction. Reference Table 602 IBC. Revise code data and provide note: masonry expansion joints to be fire caulked 2. Include required panic hardware in door schedule. Note exit doors to the outside from classrooms are required exits per city code amendment to section 903.2.2 IBC. 3. Provide exit signage and illumination per section 1003.2.10 IBC 4. Landings are required at doors. Reference section 1003.3.1.5 IBC. Revise plan 5. Please clarify if door closers are to be used. If they are, provide required clearances for door approach. Reference figure 404.2.4.1ANSI A117.1 6. Indicate method of attachment of brick veneer. If anchoring method is used, provide typical cross section. |
| 03/19/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/28/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |