Permit Number: T03CM00880
Parcel: 116273910

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM00880
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2003 DAN CASTRO ZONING REVIEW Approved
04/23/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: 141 S. Foxes Meadow
REVIEWER: Doug Williams
DATE: 30 April 2003
ACTIVITY NUMBERS: T03BU01021 & T03CM00880

SUMMARY: Engineering Division has reviewed the Site/Grading plan received on 24 April 2003. Approval is not recommended at this time. Please address the following comments:

GRADING PLAN COMMENTS

1. Please provide General Grading Notes. Grading shall conform to the 2000 International Building Code - local amendment (Chapter 36 - Excavation and Grading), and should be clearly stated on the grading plan with grading notes. Excavation and grading requirements may be accessed at: http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf.
2. This site appears to receive offsite flows from the adjacent (north) lot. Proposed finish grades at the historic acceptance location (the proposed driveway entrance area) are not clear. The plan must demonstrate how existing runoff will be accommodated in similar fashion, upon development.
3. This office highly recommends the services of a State-Registered Land Surveyor be retained for establishing the location and vertical tolerances of the layout and earthwork on this site. Please refer to Development Standard 9-04.3.0 (enclosed) for site improvement standards.

If you have any questions, I can be reached at 791-5550 extension 1189 or Dwillia1@ci.tucson.az.us

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
05/01/2003 ASHOFFS1 BUILDING-RESIDENTIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
05/01/2003 ANGIE SHOFFSTALL REJECT SHELF Completed