Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL TI
Permit Number - T03CM00828
Review Name: COMMERCIAL TI
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/18/2003 | JAMES TATE | FLOODPLAIN | REVIEW | Approved | |
| 02/18/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/18/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/20/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/26/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. Include water fixture units on plumbing schedule. Reference Section 610.7, UPC and Section 302.3, Administrative Code. 2. Provide layout of natural gas piping being modified. |
| 02/26/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 02/26/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/26/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | 1. Coordinate details and plans. Reference Section 302.3, Administrative Code. 2. Provide detail for both types of exhaust fans. Reference Section 302.3, Administrative Code. 3. Ventilation air for offices is being diverted to toilet rooms. Show that 200 CFM of required outside air is being supplied to the offices. Reference Section 403.3, IMC. 4. Show exhaust duct layout on plans. Reference Section 302.3, Administrative Code. 5. Provide auxiliary drain pan for fan coil unit FC-1. Reference Section 307.2.3, IMC. 6. Provide weights of EF-1 and IH-1. Provide roof framing details. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/12/2003 | ELAINE ROSE | APPROVAL SHELF | Stop |
| 02/18/2003 | ANY | OUT TO CUSTOMER | Stopped |
| 02/18/2003 | ANY | REJECT SHELF | Stopped |