Permit Number: T03CM00828
Parcel: 107110850

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM00828
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2003 JIM EGAN FIRE REVIEW Approved
02/18/2003 JAMES TATE FLOODPLAIN REVIEW Approved
02/18/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
02/18/2003 ROBERT SHERRY WATER REVIEW Approved
02/20/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/26/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved 1. Include water fixture units on plumbing schedule. Reference Section 610.7, UPC and Section 302.3, Administrative Code.
2. Provide layout of natural gas piping being modified.
02/26/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
02/26/2003 GERRY KOZIOL WWM REVIEW Approved
02/26/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. Coordinate details and plans. Reference Section 302.3, Administrative Code.
2. Provide detail for both types of exhaust fans. Reference Section 302.3, Administrative Code.
3. Ventilation air for offices is being diverted to toilet rooms. Show that 200 CFM of required outside air is being supplied to the offices. Reference Section 403.3, IMC.
4. Show exhaust duct layout on plans. Reference Section 302.3, Administrative Code.
5. Provide auxiliary drain pan for fan coil unit FC-1. Reference Section 307.2.3, IMC.
6. Provide weights of EF-1 and IH-1. Provide roof framing details.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2003 ELAINE ROSE APPROVAL SHELF Stop
02/18/2003 ANY OUT TO CUSTOMER Stopped
02/18/2003 ANY REJECT SHELF Stopped