Permit Number: T03CM00823
Parcel: 12009309B

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM00823
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
03/11/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
03/11/2003 JIM EGAN FIRE REVIEW Approved
03/11/2003 JIM TATE FLOODPLAIN REVIEW Approved
03/18/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Page 2 of 2 C:\11data\Commercial\Reviews\816-30015-22 (173).doc
ELECTRICAL:
Equipment E93 (an air compressor) is listed at 114 amps both in the equipment schedule
on Sheet E1and the load calculations on Sheet E4, however it is attached to a 100 amp
disconnect with an 80 amp fuse as shown on the one-line diagram on Sheet E4. Please
clarify. The neighboring air compressor is smaller and is connected to a larger
disconnect (200 amp).
03/18/2003 EROSE1 WATER REVIEW Denied
03/18/2003 EROSE1 WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2003 ELAINE ROSE OUT TO CUSTOMER Completed