Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM00823
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/11/2003 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 03/11/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/11/2003 | JIM TATE | FLOODPLAIN | REVIEW | Approved | |
| 03/18/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | Page 2 of 2 C:\11data\Commercial\Reviews\816-30015-22 (173).doc ELECTRICAL: Equipment E93 (an air compressor) is listed at 114 amps both in the equipment schedule on Sheet E1and the load calculations on Sheet E4, however it is attached to a 100 amp disconnect with an 80 amp fuse as shown on the one-line diagram on Sheet E4. Please clarify. The neighboring air compressor is smaller and is connected to a larger disconnect (200 amp). |
| 03/18/2003 | EROSE1 | WATER | REVIEW | Denied | |
| 03/18/2003 | EROSE1 | WWM | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |