Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM00802
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation of the multi-purpose building per Table 403.3, IMC 2000. |
| 03/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanout on horizontal drain line from L-1H to main building drain. Reference Section 704.1(1), UPC. 2. A mop sink is not an approved receptor for a P/T discharge. Reference Section 608.5, UPC. 3. The check valve and shut-off valve, shown at the cold water inlet of the water heater, prevent the proper operation of the thermal expansion tank. Reference Section 608.3, UPC. |
| 03/05/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/06/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/13/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs wastewater design review of public sewer casing between buildings |
| 03/28/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Indicate grounding electrode system @ M.P. building 2.Size grounding electrode and bonding conductors @ MPR. 3. 2" conduit too small for 400 amp feeder? Please clarify. Parallel Feeders etc.. 4.Provide all conduit and conductor sizes @ riser diagram. 5.Indicate feeder-conductor sizes at existing ses#1. 6. Clarify (service equipment both identified as (E) SES#2) ? |
| 04/18/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Toilet centerline to be a maximum of 18 inches from wall. Reference section 604.2 ANSI A117.1. Revise plan 2. Thirty-inch approach clearance for drinking fountain to be centered on the unit. Reference section 602 ANSI A117.1. Revise plan 3. Provide accessible parking adjacent to multipurpose room. Reference section 1106.5 IBC 4. Provide allowable area calculations for building expansion per section 506 IBC 5. Occupant load to be factored at one per seven square feet. Reference Table 1003.2.2.2 IBC. Revise calculations 6. Provide occupant load signage per section 1003.2.2.5 IBC. 7. A one-hour fire partition with forty-five minute opening protection is required for storage room # 505. Reference section 302.1.1 IBC. Revise plans 8. Indicate minimum clearances from grade for weep screed per section 2512.1.2 IBC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/21/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 04/18/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |