Permit Number: T03CM00802
Parcel: 117062670

Address:
200 E 13TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM00802
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation of the multi-purpose building per Table 403.3, IMC 2000.
03/05/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanout on horizontal drain line from L-1H to main building drain. Reference Section 704.1(1), UPC.
2. A mop sink is not an approved receptor for a P/T discharge. Reference Section 608.5, UPC.
3. The check valve and shut-off valve, shown at the cold water inlet of the water heater, prevent the proper operation of the thermal expansion tank. Reference Section 608.3, UPC.
03/05/2003 ROBERT SHERRY WATER REVIEW Approved
03/06/2003 JIM EGAN FIRE REVIEW Approved
03/13/2003 GERRY KOZIOL WWM REVIEW Denied Needs wastewater design review of public sewer casing between buildings
03/28/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. Indicate grounding electrode system @ M.P. building 2.Size grounding electrode and bonding conductors @ MPR. 3. 2" conduit too small for 400 amp feeder? Please clarify. Parallel Feeders etc.. 4.Provide all conduit and conductor sizes @ riser diagram. 5.Indicate feeder-conductor sizes at existing ses#1&#2. 6. Clarify (service equipment both identified as (E) SES#2) ?
04/18/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Toilet centerline to be a maximum of 18 inches from wall. Reference section 604.2 ANSI A117.1. Revise plan
2. Thirty-inch approach clearance for drinking fountain to be centered on the unit. Reference section 602 ANSI A117.1. Revise plan
3. Provide accessible parking adjacent to multipurpose room. Reference section 1106.5 IBC
4. Provide allowable area calculations for building expansion per section 506 IBC
5. Occupant load to be factored at one per seven square feet. Reference Table 1003.2.2.2 IBC. Revise calculations
6. Provide occupant load signage per section 1003.2.2.5 IBC.
7. A one-hour fire partition with forty-five minute opening protection is required for storage room # 505. Reference section 302.1.1 IBC. Revise plans
8. Indicate minimum clearances from grade for weep screed per section 2512.1.2 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2003 LISA LESNY OUT TO CUSTOMER Completed
04/18/2003 ANGIE SHOFFSTALL REJECT SHELF Completed