Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM00801
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation of the multi-purpose building per Table 403.3, IMC 2000. |
| 03/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Increase size of VTR to equal the cross-sectional area of the required building sewer. Reference Section 904.1, UPC. 2. A mop sink is not an approved receptor for a P/T discharge. Reference Section 608.5, UPC. 3. The check valve and shut-off valve, shown at the cold water inlet of the water heater, prevent the proper operation of the thermal expansion tank. Reference Section 608.3, UPC. 4. Provide roof drain design for Health Office addition and P.E. Space building. |
| 03/05/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/06/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/28/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Install or indicate required maint. receptacles @ mechanical equipment. 2.Indicate grounding electrode system at building MPR. |
| 04/17/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide an accessible route to the PE building. Reference section 1104.2 IBC 2. Provide minimum number of accessible entrances per section 1105.2 IBC 3. Landings are required at all exit doors. Reference section 1003.3.1.5 IBC 4. Include allowable area calculations for addition to existing building. 5. Deferred submittal for the metal building requires approval of the Building Official. Submit a letter of request for deferment with approximate time of submittal. 6. Occupant load factor for PE building is 7 per square foot net. Reference table 1003.2.2.2 IBC. Revise calculations 7. Revise plumbing fixture count to reflect Table 2902.1. 8. Door to room 42A does not have the required clearances for accessibility. Reference table 404.2.4.1 ANSI A117.1. Revise plan 9. Storage rooms 101/102 are required to be separated from major use by a one-hour fire partition with 45-minute openings. Reference section 302.1.1 IBC. Provide detail of listed fire wall and location 10. Panic hardware is required on exit doors of PE building. Indicate on door schedule. 11. Centerline of toilet to be a maximum of 18 inches from wall. Reference section 604.2 A117.1 ANSI. Revise plan |
| 05/07/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs manhole tap permit |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/05/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |