Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Permit Number - T03CM00789
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 10/21/2003 | DAN CASTRO | NPPO | REVIEW | Approved | |
| 11/18/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Mechanical Comments 1. Comment not addressed. Multi-family structures are to be designed in accordance with the International Mechanical Code, 2000. 2. Comment not addressed. Provide complete energy code compliance calculations. Reference Section 101.3.1, International Energy Compliance Code, 1998. 3. Comment not addressed. Provide service space for evaporative cooler. Reference Section 306.6, IMC 2000. 4. Comment not addressed. Provide mechanical ventilation for first floor bathroom in accordance with Section 403.1, IMC 2000. Plumbing Comments 1. Comment not addressed. Provide complete plumbing plan, including waste and vent isometrics. Reference Section 302.3, Uniform Administrative Code 1997. 2. Comment not addressed. Provide water pressure and water pipe sizing calculations. Include all fixtures connected to the existing water line from the meter. Reference Section 610.1, UPC 1994. 3. Recalculate plumbing schedule using the values shown on Tables 6-3, 7-3 and A-2, UPC 1994. 4. Comment not addressed. Provide fixture descriptions for all plumbing fixtures. Reference Section 302.3, Uniform Administrative Code 1997. 5. Comment not addressed. Provide drainage piping calculations (on plans) in accordance with Sections 702.0 and 703.0, UPC 1994 with AZ State amendments. 6. Comment not addressed. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998. |
| 11/20/2003 | ASHOFFS1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/20/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |