Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T03CM00789
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/25/2003 | DAN CASTRO | ZONING | REVIEW | Denied | 1. Maximum 4 units allowed for this property, structural drawings show a 5th unit being added on. 5th kitchen may not be allowed without a variance. 2. Commercial site plan review required for addition, since there are 4 units existing. Refer to D.S. 2-02 for site plan content and specifications. 3. Per Patricia Gehlen, a site plan has been approved and must be submitted with any new/revised site plans submitted. |
09/10/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Multi-family structures are to be designed in accordance with the International Mechanical Code, 2000. 2. Provide complete energy code compliance calculations. Reference Section 101.3.1, International Energy Compliance Code, 1998. 3. Provide service space for evaporative cooler. Reference Section 306.6, IMC 2000. 4. Provide mechanical ventilation for first floor bathroom in accordance with Section 403.1, IMC 2000. |
09/10/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide complete plumbing plan, including waste and vent isometrics. Reference Section 302.3, Uniform Administrative Code 1997. 2. Provide water pressure and water pipe sizing calculations. Include all fixtures connected to the existing water line from the meter. Reference Section 610.1, UPC 1994. 3. Recalculate plumbing schedule using the values shown on Tables 7-3 and A-2, UPC 1994. 4. Provide fixture descriptions for all plumbing fixtures. Reference Section 302.3, Uniform Administrative Code 1997. 5. Provide drainage piping calculations (on plans) in accordance with Sections 702.0 and 703.0, UPC 1994 with AZ State amendments. 6. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998. |
09/11/2003 | MARTIN HAEBERLE | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Indicate size and type of feeder to be used for subpanel |
09/11/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Footprint on site plan differs from the architectural floor plan. Revise plan 2. Provide a code analysis sheet including allowable area calculations. See submittal requirements. 3. Clarify property line location in relation to addition. Fire separation and protection of openings required at property line. Revise plans and include details for firewall. 4. Provide structural calculations for the proposed expansion. Include new addition and demo areas. 5. Opening for the guardrail may not allow a sphere of 4" to penetrate it. Revise plans 6. Provide smoke detector at top of stairs |
09/16/2003 | MELISSA POULIN | WWM | REVIEW | Denied | Needs WWM review of location/method of connection to public sewer/previous permits/user fees |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/21/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
09/17/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |