Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM00772
Parcel: 117050720

Address:
330 E 7TH ST

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM00772
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q While reviewing the clerestory window change that was submitted, it was noted on Sheet S3.0 that the lintel over these windows was not sized. Further, while trying to see if the lintel could possibly be sized on Detail 240 which is referenced in the upper left corner of the framing plan on Sheet S3.0, it was discovered that Detail 240 does not exist. Please clarify.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q How does the gas piping layout change based on omitting one mechanical unit and increasing the size of another? Does the condensate line layout also change? Please coordinate this mechanical change on the plumbing drawings.

ELECTRICAL:

q How does the electrical circuiting change based on omitting one mechanical unit and increasing the size of another? Please coordinate this mechanical change on the electrical drawings.

-End of Review-

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2003 ELAINE ROSE OUT TO CUSTOMER Completed