Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM00772
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/19/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q While reviewing the clerestory window change that was submitted, it was noted on Sheet S3.0 that the lintel over these windows was not sized. Further, while trying to see if the lintel could possibly be sized on Detail 240 which is referenced in the upper left corner of the framing plan on Sheet S3.0, it was discovered that Detail 240 does not exist. Please clarify. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q How does the gas piping layout change based on omitting one mechanical unit and increasing the size of another? Does the condensate line layout also change? Please coordinate this mechanical change on the plumbing drawings. ELECTRICAL: q How does the electrical circuiting change based on omitting one mechanical unit and increasing the size of another? Please coordinate this mechanical change on the electrical drawings. -End of Review- |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/19/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |