Permit Number - T03CM00760
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/29/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise ventilation calculations to show how much outside air is being provided to each room. Include all rooms. Reference Section 403.3, IMC 2000. 2. Revise ventilation calculations to show which heat pump actually supplies each room (not all rooms are supplied by all 4 heat pumps). 3. The occupant load for a library is 30 people per 1000 square feet. 4. Include the amount of outside air to be supplied by each heat pump. |
| 12/29/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/29/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |